Intelligent Data Centres Issue 02 | Page 64

UNCOVERING THE LAYERS tunnel. For a 1U server for example the pressure drop is around 350 pascals, but this does depend on the components inside the server. Fans that sit inside a 1U server are typically at best 25% efficient and it is a commonly known fact that smaller fans are less efficient than larger ones. We can now use the simple equation, ηP e = ∆P V F , again to determine the electrical power that small less efficient fans require to overcome the server pressure drop at one cubic metre per second assuming no air has wondered off somewhere else in the data centre. This yields an accumulated fan power of 1.4kW. But just how much thermal power can these fans remove? For this answer, we need to employ the steady state thermodynamic relationship of P T = ρc p V F ∆T, making use of the density of air, ρ (=1.22kg/m 3 ), its specific heat capacity at constant pressure, c p (=1006J/kg/K) and the temperature increase (delta-T), ∆T, across the servers. Now we must make a guess at the delta-T. 64 Issue 02 We can try a range, say five, 10 and 15ºC, which with the same flow rate of one cubic metre per second we obtain the thermal power that is injected in the airstream in passing through racks of servers of 6136W, 12273W and 18410W for the three-respective delta-T values. It is then easy to see that in complete ideal conditions, the small server fans respectively consume 18.6%, 10.3% and 7.1% of the total server power assuming no losses in the airflow. Given that these simple equations are based on a lot of assumptions that would yield conservative approximations, it is not unreasonable to say that IT fan power can consume more than 7% of the power of a typical 1U server. It is now very tempting to add all of these figures together to show how partial PUE is affected by the rack delta-T. Gains in reducing end use energy demand of data centres are clearly best addressed by analysing the full integrated system. ◊ WE ARE ON A CRUSADE TO APPROACH DATA CENTRES AS INTEGRATED SYSTEMS AND OUR EXPERIMENTS ARE GEARED TO INCLUDE THE FULL INFRASTRUCTURE WHERE THE FACILITY HAS IT IN IT. www.intelligentdatacentres.com