LATEST INTELLIGENCE ENERGY COMPARISON STUDY, DUBAI AND ABU DHABI PRESENTED BY Download whitepaper here Munters Energy Comparison Study Modelling Information This report presents the study undertaken for Munters on the comparison of the energy and water performance of the Munters OASIS/DCiE cooling units against other traditional cooling methods, namely legacy air cooled chiller, water cooled chiller, and high efficiency air cooled chiller. The modelling is based on a representation of the data centre electrical and cooling infrastructure. The electrical infrastructure is composed of electrical equipment to the IT whitespace, the cooling system and other loads, such as BMS system, lighting, etc. This study focuses on the following locations: Dubai and Abu Dhabi The cooling system consists of the cooling equipment serving the IT whitespace, typically CRAH units and associated chilled water cooling plant, mass air free cooling units, and cooling equipment serving other loads, such as split system for battery rooms, etc. The analysis focuses on estimating energy and water efficiency using the following metrics: Power usage effectiveness (PUE): measured as the ratio of estimated whole facility energy usage and IT energy usage; Water usage effectiveness (WUE): measured as the ratio of whole facility water usage and IT energy usage. The metrics are analysed on an annual basis. A similar process is modelled for the water usage. The modelled data centre is based on the following: two data halls of design IT capacity of 1,000kW each; Electrical distribution to the IT based on a 2N system with 2(N+1) UPS module. n Download whitepapers free from www.intelligentcio.com/me/whitepapers/ 20 INTELLIGENTCIO www.intelligentcio.com