■ ■ Be limited only to specific conditions and configurations upon which the EJ was rendered and should be based upon reasonable performance expectations for the recommended firestop system ■ ■ under those conditions; Be accepted only for a single, specific job and project location and should not be transferred to any other job or project location without a thorough and appropriate review of all aspects of the next job or location’s circumstances. Basic Requirements to be mentioned in the EJ Certificate Proper EJs should: ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ Be presented inappropriately descriptive written form with or without detailed drawings where appropriate; Clearly, indicate that the recommended firestop system is an EJ; Include clear directions for the installation of the recommended firestop system; Include dates of issue and authorization signature as well as the issuer’s name, address and telephone number; Reference tested system(s) upon which design (EJ) is based on; Identify the job name, project location and firm EJ is issued to along with the non-standard conditions and rating supported by the EJ; Have proper justification (i.e. UL, ULC, Intertek, SWRI or another independent laboratory system(s) and or opinions); Provide complete descriptions of critical elements for the firestop configuration. 73