Firestopping Book Firestopping Book | Page 60

CODES AND STANDARDS The code text in NBC 2016, section 3.4.5 & 3.4.5.4 requires through penetrations to be protected by fire stop systems having the same fire-resistance rating as that of the floor/wall. To establish the fire-re- sistance rating of the firestop system, the National Building code of India recommends using accepted standards. In India, IS 12458 standard is available for use in case of the firestop fire-resistance test. IS 12458 standard in India, is similar in requirement and test methodology as ASTM E814 and UL 1479 standards. In the US Building code IBC 2015, the code text in Section 714.3.1 requires through penetrations to be protected in accordance with Section 714.3.1.1 (as part of the fire-resistance-rated assembly) or Section 714.3.1.2 (by a through- penetration firestop system, tested and listed per the ASTM E 814 or UL 1479 standard). However, Section 714.3.1 includes an exception that allows two methods for protecting penetrations in lieu of a system tested in accordance with ASTM E 119 or UL 263 (see Section 714.3.1.1), or ASTM E 814 or UL 1479 (see Section 714.3.1.2). This exception is limited to steel, ferrous or copper pipes, tubes or conduits and focuses on the protection of the annular space. Also, the exception is limit- ed to the non-combustible pipes, tubes or conduits mentioned and would exclude any type of combustible penetrants such as cables, insulated wiring, plastic pipes or items such as ducts, chimneys or combustion appliance vents.