Firestopping Book Firestopping Book | Page 185

Generic Spec - “Penetrations and joints in fire rated elements should assure same fire rating as the element they go through.” At the same time, if the project specifications are comprehensive and well-studied, it not only provides a good clarity to the contractor, but also helps the right budgeting and compliance with national building codes and standards. The comprehensive specification text such as the one mentioned below can be referred to as an example. Comprehensive Specification - “For large openings and complex penetrations made to accommodate cable trays and bundles, multiple steel and copper pipes, Pre-formed block CFS BL made from intumescent polyurethane material for temporary or permanent firestop sealing around cables, cable bundles and conduits. Surface burning characteristics according UL 723 (ASTM E84- 01): Flame spread index 10 and smoke development index 15. The density is 0.27 g/cm³ and the expansion temperature (intumescent activation) is around 392 °F (200°C). Seismic tested on mechanical performance, smoke and fire-ratings. Application to be done by HAFSC (_____ accredited firestop specialty contractor) and applicator needs to submit Documanager generated report with all application photos and relevant UL 1479 certificates or EJ solution given by manufacturer. For the information of readers, this book also contain the annexure A, which highlights few firestop test reports from UL or Intertek laboratories. This is provided to the reader for reference purposes only as there are many such systems available among many manufacturers and these are only some examples. 185