Modem building codes are also starting to recognize the importance of minimizing sound between tenant separations. 2012 Model Residential Building Code requires that an STC of 50 be maintained for multi-family residential dwellings. This requirement ensures that sound transmission between occupied spaces is kept to a minimum. Sound transmission is a growing concern in today’s construction industry. Firestop products are being installed to not only restrict the passage of fire and toxic gasses but also to minimize sound transmission between occupied spaces. There are test standards that are specifically designed, such as ASTM E-90 to evaluate the performance of these products. Like ASTM test for firestopping, the firestop product is part of an overall STC assembly. A separation wall or floor that has an STC of 45 for example, can not be increased to a 50 by just adding a firestop product that may have been tested up to a 50 in accordance with ASTM E-90. The product can only provide an equivalent rating up to its tested rating with the assembly in which it is installed. (Fig 6.2 Typical ASTM E-90 Configuration) 179