Firestopping Book Firestopping Book | Page 172

Because the L rating test is optional within the UL 1479 test standard, code users must not simply assume that a firestop system tested to the UL standard will comply and must verify that the firestop system being used has actually been tested and received an L rating. The code specifies that the amount of leakage permitted cannot exceed 5.0 cubic feet per minute (cfm) per square foot of opening for each penetration, or a total leakage rate of 50 cfm for any 100 square feet of wall or floor area. Having the L rating requirement within the code provides a specific means to evaluate the capabilities of the system and eliminates the subjective requirements that smoke barriers needed to “limit,” “restrict” or “resist” the passage of smoke. A specified performance level reduces the inconsistent application of the requirements and helps code users know exactly what level of performance is required. It is important to point out that penetration systems must be evaluated for their L rating at “both the ambient temperature and elevated temperature tests.” While it is permissible for an intumescent F- or T-rated firestop system to leave a gap between the penetrant and firestop material when it is initially installed (due to the fact the intumescent will expand to close the gap when the temperature at the penetration increases), an L-rated system must provide an effective seal both at its original installation and when or if it is exposed to the increased temperatures of a fire. Because the purpose of the L rating is to stop the spread of smoke, the code recognizes that smoke could be located away from the fire in a place where the temperature has not elevated to the point that it would cause an intumescent material to expand and fill any gaps that would allow for the passage of smoke. It is because of this need to stop cold smoke that the code requires the L-rated system to be evaluated at both ambient temperatures and an elevated temperature of 400oF.