Firestopping Book Firestopping Book | Page 147

The last sentence of Section 715.4 requires the spandrel wall to comply with the requirements of Section 705.8.5. This coordinates with the requirements from Section 715.5 and will be discussed with that code section. The exception within Section 715.4 recognizes that curtain wall assemblies with vision glass that extends to the floor cannot meet the test criteria in ASTM E 2307 and that prior to the 2009 IBC these systems could be tested using conditions specified within the exception. The option of using materials or systems that have been subjected to an ASTM E 119 time-temperature fire condition under positive pressure should provide a reasonable level of protection. This will allow designs or systems that were tested and used in the years prior to the development of the ASTM E 2307 standard. Figure 5.9 illustrates the location of the glazing and the requirements of the exception. VISION GLASS EXTENDS TO FINISHED FLOOR LEVEL APPROVED MATERIAL SECURELY INSTALLED TO SEAL VOID. PROTECTION IS AT LEAST EQUAL TO TIME PERIOD OF FLOOR ASSEMBLY. MATERIAL CAPABLE OF RESISTING PASSAGE OF FLAME AND HOT GASES UNDER CONDITIONS OF THE ASTME E119 TIME- TEMPERATURE CONDITIONS. (Fig 5.9 Protection of Floor/Wall Intersection with Full-Height Glazing) 147