IBC Guidelines regarding Inspections: ■ ■ ■ ■ ■ ■ 110.3.6 Protection of joints and penetrations in fire-resistance rated assemblies, smoke barriers and smoke partitions shall not be concealed from view until inspected and approved. 107.1.1 - Information on Construction Documents shall be of sufficient clarity to indicate the location, nature and extent of the work proposed and show in detail that it will conform to the provisions of this codes 107.3.4.1-Deferred submittals Deferred submittals are defined as those portions of the design that are not submitted at the time of the application and that are to be submitted to the building official within a specified period. IBC Special Inspections ■ ■ ■ ■ ■ ■ 1705.16 Fire-resistant penetrations and joints. In high-rise buildings or in buildings assigned to Risk Category III or IV in accordance with Section 1604.5, special inspections for through-penetrations, membrane penetration firestops, fire-resistance joint systems, and perimeter fire barrier systems that are tested and listed 1705.1.1 Special cases. Special inspections shall be required for proposed work that is, in the opinion of the building official, unusual in its nature ASTM standards required in 1705.16 for inspection procedures (E2174-04 and E2393-04). 125