Firestopping Book Firestopping Book | Page 108

MALL TENANT SPACE JOINT PROTECTION REQUIRED FOR FLOORS OUTSIDE OF MALL FLOORS “WITHIN” THE MALL DO NOT REQUIRE FIRE-RESISTIVE JOINT PROTECTION (Fig 4.7 Floor Joints Within a Mall) When using the calculated fire-resistance provisions of Section 722.2.1.3 for joints between concrete precast wall panels, the code states that the unprotected joints are to be included when determining the percentage of openings allowed by Table 705.8. In addition, the fact that the exception in Section 715.3 allows a joint to be tested and fire-resistance-rated from only one side at 5 feet appears to indicate the code intends joints to be considered as openings and included within the percentage of wall openings allowed by Section 705.8. If non-sprinklered buildings are allowed nonrated joints at 5 feet by Item 7 in Section 715.1, then there would be no reason for the exception in Section 715.3 to address the nonsymmetrical joints with a fire separation distance greater than 5 feet unless the joints are expected to be considered as either protected or non-protected openings by Section 705.8.