EnergySafe Magazine Winter 2015, issue 40 | Page 12

12 Electrical news Case study: Dangers of non-compliant switchboards Article submitted by David Webb, DRC Switchboards, NESMA Technical Representative on Standards A licensed electrical inspector (LEI) was requested to attend an electrical installation consisting of a Pillar and a Form 3b Main Switchboard. Both boards were assigned a rating of 1600 amps. The inspector was unsure of the suitability of both boards considering AS/NZS 3000 wiring Rules Clause 2.9: 2.9.3.2 Suitability Switchboards shall be suitable to withstand the mechanical, electrical and thermal stresses that are likely to occur in service. Switchboards complying with the relevant requirements of the AS/NZS 3439 series of Standards are considered to meet the requirements of Clause 2.9.3. Note: 1 See also Clause 7.2.8.1 regarding segregation requirements for safety services. 2 See also Clause 2.5.5 regarding requirements for protection against the effects of arcing fault currents. As a precaution, the Kiosk protection was subsequently set below 800 amps. The inspector referred the matter to ESV for further assistance with evaluation of the design. ESV engaged NESMA (the National Electrical Switchboard Manufacturing Association) to provide an independent representative familiar with the details of the standard and forms of separation to assist with this evaluation. On inspection The switchboards appeared to be noncompliant with AS/NZS 3439.1-2002 and AS/NZS 3000-2007, and therefore noncompliant electrical equipment as per Section 54 of the Electrical Safety Act. Specifically Sections 8.2.1, 8.2.3 and 8.2.7 of AS/NZS 3439.1: Heat rise, Mechanical Strength, IP Rating and Separation. In the absence of supporting verification, the following was agreed by the switchboard manufacturer who also attended the site inspection. IP rating Reference Clause: AS/NZS 3439.1-2002 8.1.1 (g)— The Pillar was nominated as IP 56. There was no evidence of testing or verification to AS/NZS 60529. Louvres were punched into the side and inconsistent with the nominated IP65 rating. The main switchboard was nominated as IP 44. There was no evidence of testing or verification to AS/NZS 60529 on the sealing provided on the switchboard. Separation Reference Clause AS/NZS3439.1-2002 8.1.1 (g)— There was no separation to Form 3b or derivation, or by calculation as required by AS/NZS 3000 Clause 2.5.5. Note: An attempt was made to make a Form 3b switchboard by wrapping busbars using PVC tape. Tape is specifically noted as non-acceptable in AS/NZS 3439.1-2002 Clause 7.4.2.1. Mechanical strength and short circuit capacity Reference Clause AS/NZS 3439.1-2002 8.1.1 (c)— There was no evidence of any bus bar supports. The bus bars that were attached to the breakers were not consistent with the manufacturer’s recommendations and no verification test was provided. Temperature rise Reference Clause AS/NZS 3439.1-2002 8.1.1 (a)— There was no ventilation on the main switchboard. The Main Bus was of insufficient size, for 1600amps. No evidence to support the rating of 1600amps was provided, by either test result or verification as allowed in AS/NZS 3439.1-2002 Clause 8.2.1.1. Note: Compliance can be verified using AS 3439.1 Clause 8.2.1.1, by either: »» test »» extrapolation, for example IEC 60890. Neither could be achieved in this case as there was no evidence of type testing. AS 60890 could not be used as a method of calculation. AS 60890 can be used for verification only if: »» there are no more than three horizontal partitions. »» there is ventilation in the horizontal partitions. (The standard nominates horizontal partitions to have 50 per cent ventilation) »» there are inlet or outlet ventilations. The standard nominates the outlet to be larger than the inlet by a factor of 1.1. Additional requirements of Clause 8.1 While the switchboards inspected did not have evidence of compliance with subsections (a), (c) and (g), the other subsections (b), (d), (e) and (f) of AS/NZS 3439.1-2002 Clause 8.1 are also required. Outcome The switchboard manufacturer volunteered An example of a 3200amp main switchboard with no evidence of compliance with AS/NZS 3000:2007 Clause 2.5.5 (not the one referred to in this article) to remove the non-compliant electrical equipment and replace it with equipment that was compliant. They also agreed to pay all costs associated with the removal, rebuilding, shut down costs, electrical contractor’s costs and service charges. David Webb represents DRC Switchboards. For further information telephone (03) 9587 4499. Consequences: non-compliant installations ESV has the power to: »» issue a Show Cause Notice »» issue proceedings under Section 54 of the Electricity Safety Act »» request a list of all products supplied »» investigate all products supplied by a company for a period of up to three years.