e-Showcase Sungrow PV Grid-Connected Inverters 2015~2016 | Page 49

String Inverter Input Side Data SG3KTL-D SG3K6TL-D SG4K6TL-D SG5KTL-D Max. PV input power Max. PV input voltage Startup voltage Nominal input voltage MPP voltage range MPP voltage range for nominal power No. of MPPTs Max. number of PV strings per MPPT Max. PV input current Max. current for input connector 3300W 600V 150V 345V 125~560V 150~520V 2 1 22A (11A/11A) 20A 3900W 4900W 5400W 180~520V 220~520V 240~520V Output Side Data 3000W 4600W 3680W 3150W 4600W 3680W 3150VA 4600VA 3680VA 13.7A 20A 16.0A 230Vac (single phase) 180~276Vac 50Hz/60Hz 45~55Hz/55~65Hz <3% (nominal power) <0.5 %In >0.99@default value at nominal power, (adj. 0.8 leading ~ 0.8 lagging) Nominal AC output power Max. AC output power (PF=1) Max. AC output apparent power Max. AC output current Nominal AC voltage AC voltage range Nominal grid frequency Grid frequency range THD DC current injection Power factor 5000W/4600W *(Australia) 5000W 5000VA 21.7A/20A *(Australia) Protection Anti-islanding protection LVRT DC reverse connection protection AC short circuit protection Leakage current protection DC switch DC fuse Overvoltage protection Yes No Yes Yes Yes Optional No Varistors System Data Mechanical Data 98.00% 97.50% Transformerless IP65 <1W -25~60℃ (>45℃ derating) 0~100% Natural cooling 4000m (>2000m derating) LED , LCD (optional) WiFi (optional) MC4 Plug and play connector IEC61000-6-2, IEC61000-6-3, AS/NZS3100, AS4777.2, AS4777.3, VDEAR-N-4105, VDE0126-1-1, CE,G83/2, C10/11, EN50438, CGC Dimensions (W*H*D) Mounting method Weight 360*390*133 mm Wall bracket 11kg Max. efficiency Max. European efficiency Isolation method Ingress protection rating Night power consumption Operating ambient temperature range Allowable relative humidity range Cooling method Max. operating altitude Display Communication DC connection type AC connection type Certification * When the country parameter of SG5KTL-D is set to Australia, nominal output is 4600W and maximum output current is 20A. Circuit Diagram DC Switch ( optional) + DC1 + DC2 - Functional Safety &Protective Circuit DC EMI Filter MPPT1 Boost DC EMI Filter MPPT2 Boost Communication Interface: Wi-Fi (optional) Inversion Circuit AC EMI Filter AC Reactor Grid L N Relay PE LED Indicator, LCD Display (optional) 47