String Inverter
Grid Type
230V/400Vac
Input Side Data
Max. PV input power
Max. PV input voltage
Startup voltage
MPP voltage range
MPP voltage range for nominal power
No. of MPPTs
Max. number of PV strings per MPPT
Max. PV input current
Max. current for input connector
67500W
1000V
620V
570~950V
570~850V
1
12
120
12A
Output Side Data
Nominal AC output power
Max AC output power (PF=1)
Max. AC output apparent power
Max. AC output current
Nominal AC voltage
AC voltage range
Nominal grid frequency
Grid frequency range
THD
DC current injection
Power factor
Protection
Anti-islanding protection
LVRT
DC reverse connection protection
AC short circuit protection
Leakage current protection
DC switch
AC switch
DC fuse
PV String detection
ARC detection
DC Overvoltage protection
AC Overvoltage protection
60000W
66000W
66000VA
96A
3P+N+PE/3P+PE, 230/400Vac
310~480Vac
50Hz/60Hz
45~55Hz/55~ 65Hz
<3% (Nominal power)
<0.5%In
>0.99@default value at nominal power, (adj. 0.8 leading ~ 0.8
lagging)
Yes
Yes
Yes
Yes
Yes
Yes
Optional
Yes
Optional
Optional
DC Type II DIN rail surge arrester (40KA)
Optional AC Type II DIN rail surge arrester (40KA)
System Data
Mechanical Data
Max. efficiency
Max. European efficiency
Isolation method
Ingress protection rating
Night power consumption
Operating ambient temperature range
Allowable relative humidity range
Cooling method
Max. operating altitude
Display
Communication
DC connection type
AC connection type
Certification
Dimensions (W*H*D)
99.00%
Mounting method
98.70%
Weight
Transformerless
IP65
<1W
-25~60℃ (>50℃ derating)
0~100%
Smart forced air cooling
4000m (>3000m derating)
Graphic LCD
RS485
MC4/Screw Clamp terminal
Screw Clamp terminal
VDE0126-1-1, EN62109-1, EN62109-2, G59/3, BDEW, GB/T
19964, GB/T 29319
634*959*267mm
Wall bracket
55kg
Circuit Diagram
DC Fuse
DC BUS
DC In
DC EMC
DC SPD
RELAY
Inverter
circuit
AC
Reator
AC
EMC
L1
L2
L3
N
GRID
DC Switch
PE
25