e-mosty June 2017: Osman Gazi B. US Suspension. Hålogaland B. e-mosty June 2017: Suspension Bridges | Page 60

3.7 System Commissioning and Operation The system commissioning process included the evaluation of the mechanical, electrical and controls system in the field. Extensive checklists were used to evaluate the system and its performance. The process also included soapy water testing of the cable wrap and sealants to identify air leaks, as well as air flow trials to further evaluate system performance. The Westbound Bridge dehumidification system was commissioned and operational in early 2014 while the Eastbound Bridge system was commissioned and operational by late 2015. The systems have remained in general operation since. Figure 25: Sensors in NEMA 4X sensor box The NEMA enclosure standards are defined in North America by the National Electrical Manufacturers Association (NEMA). For this application, the contract required an enclosure rating of 4X setting a standard for both corrosion protection, commonly used near salt water, and water tightness. Flow, temperature, and humidity are monitored at injection and exhaust points, in addition to pressure at injection points. The injection pressure is both recorded and directly fed back to the dehumidification plant controllers to allow active control of the fan speed for a consistent injection pressure. A weather station is also installed to record weather data and the system feeds this data back to the plant room as well. The system is accessed by either an operator interface terminal (OIT) in the plant rooms or remotely through the SCADA computer located in the MDTA administration building. The system is also accessible through a secure web-enabled interface. Data collected and analyzed from the SCADA systems on both bridges illustrate the systems are performing as intended. The graphs in Figure 26 demonstrate the efficacy of the Westbound System in two ways. The left graph plots the relative humidity over time for the first two years of operation to evaluate the cable drying process. As can be seen, the relative humidity starts out quite high indicating the prevalence of moisture in the cable. However, within approximately the first nine months, the relative humidity has dropped and then sustained below 40% RH. The graph on the right plots the cumulative water removed over time, which is not directly measured but calculated from the relative humidity and temperature data collected. As can be seen again in the first two years, approximately 1,200 equivalent liters of water have been removed from the North Cable. Similar results have been observed for the South Cable and for the Eastbound Bridge. Figure 26: Westbound data – relative humidity over time (left); cumulative water removed over time (right) 2/2017