e-mosty June 2017: Osman Gazi B. US Suspension. Hålogaland B. e-mosty June 2017: Suspension Bridges | Page 36

o o o o o Internal and external lighting (routine maintenance) Cabling, transformer (routine maintenance) Communication system (routine maintenance) Dehumidification of main cable (routine maintenance) Hydraulic buffers (routine maintenance) 5.4 Access for Inspection and Maintenance All structures of Osmangazi Bridge are accesible for inspection, maintenance and for replacement purposes. The most suitable equipment to provide safe, efficient and effective access were chosen and provided during the design phase. For all equipment installed at high level, facilities for maintenance were designed either as permanent working platforms or as flexible mobile elevating platform. 5.3 Reporting After each major inspection, inspection reports shall be prepared which include detailed descriptions of any damage or deteriorations with pictures. Hard copies and soft copies of inspection reports are recorded. Those records will be used in planning and execution of future maintenance and repair works. The tower internal area, tower top and saddle enclosure areas, tower external faces, anchorages and caisson interiors, expansion joint areas, main cable and hangers are all designed to have permanent access as described below. The walkways of the bridge deck serve as a dedicated access lane, to be used by maintenance vehicles for reaching the designated maintenance location in a fast and efficient manner without disrupting normal traffic. After maintenance, detailed reports shall be prepared which include description of the maintenance, and maintenance costs spent. These will help and be used in planning/evaluation of alternative maintenance strategies for high cost future maintenance operations and prediciting the remaining service life of components. Access Facilities Suspended Deck Access Door & Hatch to Deck, Interior Walkway, Inspection Gantry, Access to Inspection Gantry Articulations Platforms Cable & Hanger Access to Saddles and Main Cable, Walkway on Main Cable, Cable Carriageway, Hanger Basket Tower Access Door & Hatch to Tower, Access Ladder and Platform, Access Ramp from Tower to Deck, Inspection Cradle for Tower Exterior Tower Foundation, Anchorage Block, Piers Access Door to Splay Chamber, Access Stairs in Splay Chamber, Access Door to Pier, Access to Tower Foundation Caisson Shaft Table 2: Access facilities for inspection and maintenance 2/2017