Electrical data 30RBS without hydronic module 039 045 050 060 070 080 090 100 120 140 160 Power circuit Nominal power supply V-ph-Hz 400-3-50 Voltage range V 360-440 Control circuit supply 24 V via internal transformer Maximum start-up current (Un)* Standard unit A 113.8 134.8 142.8 145.8 176.0 213.0 173.6 207.6 247.6 243.0 286.0 Unit with electronic starter option A 74.7 86.5 93.8 96.2 114.4 139.8 - - - - - COOLING Unit power factor at maximum capacity** Maximum operating power input** kW 19.5 22.3 24.5 27.9 31.2 35.8 42.3 45.6 52.5 62.4 71.6 Nominal unit operating current draw*** A 25.6 29.0 33.0 36.0 42.4 52.8 55.4 61.7 77.3 84.8 105.6 Maximum operating current draw (Un)**** 34.8 44.8 46.8 52.8 67.0 73.0 80.6 98.6 107.6 134.0 146.0 Maximum operating current draw (Un10%)† 38.0 49.2 51.4 58.4 74.8 79.6 89.0 110.3 117.5 149.6 159.2 Customer-side unit power reserve Customer reserve at the 24 V control power circuit Short-circuit stability and protection See table “Short-circuit stability current” below * Maximum instantaneous start-up current at operating limit values (maximum operating current of the smallest compressor(s) + fan current + locked rotor current of the largest compressor). Power input, compressors and fans, at the unit operating limits (saturated suction temperature 10°C, saturated condensing temperature 65°C) and nominal voltage of 400 V (data given on the unit nameplate). *** Standardised Eurovent conditions: evaporator entering/leaving water temperature 12°C/7°C, outside air temperature 35°C. **** Maximum unit operating current at maximum unit power input and 400 V (values given on the unit nameplate). † Maximum unit operating current at maximum unit power input and 360 V. ** Options * ** 96 Options No. Description Advantages Condenser with anti-corrosion post- treatment 2B Coils with factory-applied Blygold Polual treatment Condenser with pre-treated fins 3A Low temperature glycol solution 5B Very low temperature glycol solution 6B Very low noise level 15LS Protection grilles Soft starter Winter operation** 23 25 28 Fins made of pre-treated aluminium (polyurethane and epoxy) Low temperature chilled water production down to 0°C with ethylene glycol and propylene glycol. Note: With option 5B the units are equipped with traditional coils (Cu/Al). Low temperature chilled water production down to -15°C with ethylene glycol and -12°C with propylene glycol. Note: With option 6B the units are equipped with traditional coils (Cu/Al). Acoustic compressor enclosure and low-speed fans Metallic protection grilles Electronic compressor starter Fan speed control via frequency converter Improved corrosion resistance, 30RBS 039-160* recommended for urban, industrial and rural environments Improved corrosion resistance, 30RBS 039-160* recommended for marine environments Covers specific applications down to 30 RBS 039-160 0°C Frost protection down to -20°C 42 Electric heater on the hydronic module Partial heat reclaim 49 Master/slave operation 58 Main disconnect switch without fuse HP single-pump hydronic module 70 HP dual-pump hydronic module 116C Partial heat reclaim by desuperheating of the compressor discharge gas. Note: With option 49 the units are equipped with traditional coils (Cu/Al). Unit equipped with an additional field-installed leaving water temperature sensor, allowing master/ slave operation of two units connected in parallel Factory-installed main electric disconnect switch in the control box Single high-pressure water pump, water filter, expansion tank, temperature and pressure sensors. See hydronic module option. Dual high-pressure water pump, water filter, expansion tank, temperature and pressure sensors. See hydronic module option. 116B Use 30RBS Covers specific applications such as ice 30RBS 039-160 storage and industrial processes Noise emission reduction at reduced fan speed Coil protection against possible shocks Reduced compressor start-up current Stable unit operation when the air temperature is between -10°C and -20°C Hydronic module frost protection at low outside temperatures Free high-temperature hot-water production simultaneously with chilled and hot-water production Operation of two units connected in parallel with operating time equalisation 30RBS 039-160 Ease-of-installation and compliance with local electrical regulations Easy and fast installation 30RBS 039-160 Easy and fast installation, operating safety 30RBS 039-160 30RBS 039-160 30RBS 039-160 30 RBS 039-160 30RBS 039-160 30RBS 039-160 30RBS 039-160 30RBS 039-160 30RBS 039-160 with option 49 or 30RBS 0039-160 with option 6B. Winter operation option: This option allows operation of the unit down to -20°C outside air temperature due to the optimised control of the condensing temperature. One fan is equipped with a frequency converter. C A R R I E R 2 0 1 6 / 2 0 1 7