AHI Carrier Catalog | Page 818

Outdoor ambient temperature options
■■
Temperature --
Thermal and acoustic insulation 50 mm thick , with fire classification Euroclasse A2-s1 , d0 .
Cover loss : Conditions
Winter
Indoor
20 º C
50 % RH
Outdoor
-20 º C
94 % RH
9mm NBR ( std )
1790 W
2.0 % HC
50mm rock wool
437 W
0.4 % HC
Conditions
Summer
Indoor
27 º C
50 % RH
Outdoor
35 º C
40 % RH
9mm NBR ( std )
615 W
1.00 % TCC
50mm rock wool
151 W
0.24 % TCC
--
Electrical heater for protection of the components of the electric panel . This is compulsory if the outdoor temperature is lower than -8 º C WB . With an outdoor temperature ower than -16 º C WB will be compulsory a reinforced resistance .
--
Compressor with protection for low temperature ( supplementary crankcase heater ). This is compulsory if the outdoor temperature is lower than -8 º C WB .
--
Dampers with spring for automatic closing in case of a tension cut . This is compulsory if the outdoor temperature is lower than -8 º C WB .
--
Electrical heater for antifreeze protection of dampers of mixing boxs . This is compulsory if the outdoor temperature is lower than -12 º C WB .
--
Circuit of the hot water coil with antifreeze protection according to the water temperature . This is compulsory if the outdoor temperature is lower than -20 º C WB .
■■
Humidity --
Stop-drop in the indoor air coil . Recommended in cases where a high moisture content in the air is foreseen or when the air flow is high .
--
Stop-drop in the outdoor air intake .
-- Tropicalised electric panel .
--
Tropicalised motors and fans ( please consult ).
Indoor stop-drop
■■
Comfort / heating options --
Hot water auxiliary coil , with three-way valve . This optional always incorporates an anti-freeze thermostat as safety system .
--
Auxiliary electrical heaters , with one or two stages with on / off control .
Note : electrical support is not available in models 90 to 180 with top supply and centrifugal fan ( optional ).
--
Natural or propane gas burner with modulating actuator . Available for all assemblies except top and bottom outlet . With this option , it is recommended to have the differential pressostat option for detecting clogged filters .
Note : with centrifugal fan ( optional ), it is compulsory the differential pressostat for controlling the air flow that stops the burner in case of fire .
AIR TREATMENT
■■
Corrosion --
Coils ( outdoor , indoor and / or auxiliary ) with copper pipes and copper fins .
--
INERA ® coils ( outdoor , indoor and / or auxiliary ) with copper pipes and fins of an aluminium alloy , of high performance and great resistance to the corrosion .
--
Coils ( outdoor , indoor and / or auxiliary ) with copper pipes and aluminium fins with polyurethane and Blygold ® coating .
--
Condensate drain pan for the indoor circuit in stainless steel .
818 C A R R I E R 2 0 1 6 / 2 0 1 7