Physical Data
40HB/HF
80
90
120
160
Indoor circuit centrifugal fan
Nominal air flow
m3/h
4.000
4.600
6.000
7.000
Available static pressure
mm.w.c
20
20
20
20
Number / turbines
1/1
Motor output
kW
1,5
2,2
2,2
2,2
Power input
kW
1,07
1,48
1,56
1,62
Speed
r.p.m.
1.497
1.613
1.219
1.030
A
3,6
5,0
5,0
5,0
Length
mm
1.500
1.500
1.831
1.831
Width
mm
870
870
1.103
1.103
Height
mm
639
639
706
706
Weight
kg
125
128
171
181
Max. abs.current
Fan
Dimensions
Additional load of R-410A refrigerant
Aditional load per linear metre of piping for equivalent maximum lengths exceeding 7 metres:
Nominal diameter
inches
1/4”
3/8”
1/2”
5/8”
3/4”
7/8”
1”
1 1/8”
Interior section
cm
0,149
0,444
0,900
1,505
2,282
3,120
4,290
5,346
Liquid line charge
g/m
19,3
57,0
115,0
193,5
292,3
404,1
550,3
685,7
Gas line charge
g/m
-
0,2
0,4
0,7
1,0
1,4
2,0
2,5
2
Power level and sound pressure level dB(A)
AIR TREATMENT
A) The sound power level in the outdoor unit fan supply to be taken into account for the silencer operation:
38HB/HF
80
90
120
160
dB(A)
79.1
81.5
79.2
83.9
B) The sound pressure level of the outdoor unit, measured at a distance of 5 metres, in open fi eld, directivity at 2 and 1.5 m
from the ground, is:
38HB/HF
80
90
120
160
dB(A)
65.0
68.4
68.5
69.7
C) The sound pressure level of the indoor unit, with the ducted supply and discharge connections, measured at a distance of 5
metres, in open fi eld, directivity at 2 and 1.5 metres from the ground, is:
40HB/HF
80
90
120
160
dB(A)
65.9
64.6
65.2
64.2
Note: The sound pressure level depends on the installation conditions and, as such, is only indicated as a guide.
790
C
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7