DUCTABLE AIR-COOLED SCROLL CHILLERS 30PA / PAC
Minimum volume of water admissible
in the installation (cooling mode)
30PAC
STD version
Minimum volume
l
HEE version
90STD
100STD 120STD 160STD 180STD 90HEE
100HEE 120HEE 160HEE 180HEE
101
120
132
143
187
204
107
152
189
210
The calculation of the minimum water volume has been done for nominal EUROVENT conditions, only in cooling mode. This
value is applicable for the majority of refrigeration applications (group with fan -coil units).
COOLING
The electronic control for the 30PA units incorporates an auto-adaptive control for the compressor operating time based on the
time set for anti-short-cycle.
This control reduces the number of times the compressor is started up and permanently adjusts the system’s thermal inertia,
favouring the reduction of the minimum volume of water in the installation.
The size of the buffer tank can also be decreased since the unit will be stopped for less time.
Note: the buffer tan k is indispensable in installations that operate with a reduced volume of water (group with an air handling unit) or for industrial processes.
For applications with a heat pump, it is recommended that the buffer tank be used in order to maintain a stable temperature during the defrosting cycles.
Measurement conditions: in a clear field, measured at a distance of 10 metres, directivity 2 and at 1,5 metres from the ground.
30PA/PAC
Total
STD version
dB(A)
HEE version
90STD
100STD
120STD
160STD
180STD
90HEE
100HEE
120HEE
160HEE
180HEE
38,0
38,4
38,4
38,4
38,4
36,6
38,3
38,4
38,4
38,4
CONTROLS
AIR TREATMENT
Note: The sound pressure level depends on the installation conditions and, as such, is only indicated as a guide. Values obtained according to standard ISO 3744.
HEATING HEATING
Sound pressure level