AHI Carrier Catalog | Page 776

2272 R1 14 R2 1739 37 50HB/HF - 120 and 160, M0000 assembly (mm) R3 74 568 488 150 301 1075 1075 1000mm 478 * * 1824 ( ) 1000mm * ( ) * 1000mm ( ) AIR TREATMENT 665 ( ) Y 1904 X 805 32 1 2 2300 1000mm 40 1824 708 218 345 Z (*) 40 399 235 708 749 824 805 32 74 R4 2220 Both in the indoor air circuit as well as the outdoor circuit, the supply and return panels can be located in any one of the two positions indicated in the following drawings, since both panels are easy interchangeable, with the goal to leave it finalized as most convenient in each installation. 50HB/HF Centre of gravity (mm) Reactions in the supports (kg) Legend X Y Z Weight R1 R2 R3 R4 120 1.104 917 340 472 125 113 112 122 160 1.096 921 343 521 139 126 122 135 Outdoor air circulation Indoor air circulation Electric panel Power supply Door switch 1 Condensate outlet indoor circuit Æ 3/4” female thread 2 Condensate outlet outdoor circuit Æ 3/4” female thread Antivibration anchoring: rivet nut M10 Note 1: supply intake profile: 25 mm Note 2: the return frame of the indoor circuit, with filters G4+F7 as option, protrudes 50mm more Clear space to be observed for maintenance operations and unit start-up 776 C A R R I E R 2 0 1 6 / 2 0 1 7