AHI Carrier Catalog | Page 76

Schematic diagram of the hydraulic circuit (*) 30PAC with pump PLATES EXCHARGER EXPANSION VESSEL SHUT-OFF VALVE CIRCULATOR PUMP CIRCUIT DRAINAGE SAFETY VALVE DIFFERENTIAL PRESSURE SWITCH MESH FILTER (*) Mesh filter, suplied in kit for installation by the client in 30PAC (optional for 30PA). Cut-off and water regulation valves, as well as flexible hydraulic connections, can also be supplied in the kit. Circulation pumps available for 30PAC 30PAC 90STD Number Standard 3.171 of pump High-pressure (optional) 3.173 Low-pressure (optional) -- 90HEE 100STD 100HEE 120STD 120HEE 160STD 160HEE 180STD 180HEE 3.171 3.173 -- 3.172 3.173 3.171 3.172 3.173 3.171 3.172 3.174 3.171 3.172 3.174 3.171 3.173 3.174 3.171 3.173 3.174 -- 3.174 3.175 3.229 3.174 3.175 3.229 Note: These pumps can operate with glycol water (mono-ethylene glycol), although with a reduction of the available pressure (due to the flow variation with glycol water). Consult the correction coefficients in the chapter “Operation with glycol water”. Available pressure (m.w.c.) COOLING 30PA 40 3.173 30 3.175 3.174 3.172 3.171 20 3.229 10 2 1 3 4 5 6 7 8 9 10 15 20 Flow (m3/h) Number of pump 3.171 3.172 3.173 3.174 3.175 3.229 0,37 0,55 0,75 0,9 1,5 0,55 Motor output kW Maximum absorbed current A 1,4 2,0 2,3 2,7 4,0 2,0 Minimum water flow m3/h 1,2 1,2 1,2 3,0 4,8 3,0 Maximum pressure (m.w.c) 20,7 28,0 30,3 29,5 31,6 20,6 Maximum water flow m /h 5,4 4,8 6,6 9,6 15,0 9,6 Minimum pressure (m.w.c) 15,0 20,5 19,5 19,5 23,0 13,7 76 3 C A R R I E R 2 0 1 6 / 2 0 1 7