HEE version: technical characteristics
30PA
90HEE
100HEE
120HEE
160HEE
180HEE
Cooling
Cooling capacities
COOLING
Outdoor circuit
plug-fan
Net cooling capacity *
kW
18,40
21,00
25,50
31,40
35,70
Net power input **
kW
7,20
7,95
9,10
11,50
13,60
(m3/h)
Net efficiency
EER
2,55
2,64
2,81
2,74
2,62
Seasonal efficiency
Nominal air flow
ESEER ***
2,89
6500
2,99
7000
3,20
10000
3,14
12200
3,03
14000
62,7
Nominal available static pressure
(mm.w.c) 20
Maximum available static pressure
(mm.w.c) 63,7
Number / diameter
Motor output
Indoor circuit
Compressor
Electrical
characteristics
Weight
2,7
2,8
65,1
2 / 560
3,0
2 x 3,0
Power input ****
kW
1,33
1,21
1,87
2,20
(r.p.m.)
1700
1780
1500
1500
Nominal water flow
(m3/h)
3,2
3,7
4,5
5,4
6,2
Pressure drop
(m.w.c)
1,6
2,1
1,6
2,4
3,1
Minimum water flow
(m3/h)
2,5
2,9
3,4
4,1
4,6
Maximum water flow
(m3/h)
6,6
7,4
9,1
11,3
12,8
2,52
Type of hydraulic connections
Rosca gas
Diameter of connections
1 1/4” M
Type
Scroll
Number of compressors / stages / circuits
1
Oil type
Copeland 3MAF 32 cST, Danfoss POE 160 SZ, ICI
Emkarate RL 32 CF, Mobil EAL Artic 22 CC
6,2
3,0
3,3
3,3
3,3
l
Type
R-410A
Global warming potential (GWP) *****
2.088
1 1/2” M
Charge
kg
6,0
6,3
6,8
8,9
9,2
Environment impact
(tCO2e)
12,5
13,2
14,2
18,6
19,2
Electrical power supply
400 V / III ph / 50 Hz (±10%)
Power supply
Maximum absorbed Compressor
current
Fan
Dimensions
kW
45,6
1 / 560
Speed
Volume of oil
Refrigerant
70,3
1 / 500
3 Hilos + Tierra + Neutro
A
15,2
17,3
20,5
25,4
30,5
A
4,2
4,3
4,6
9,2
9,2
Control
A
0,9
0,9
0,9
0,9
0,9
Total
A
20,3
22,5
26,0
35,5
40,6
Length
mm
1117
1398
2113
Width
mm
860
860
860
Height
mm
1447
1727
Empty
kg
294
351
368
450
455
In operation
kg
298
358
376
465
468
90HEE
100HEE
120HEE
160HEE
180HEE
3,22
4,5
2,5
3,17
5,4
3,5
3,02
6,2
4,6
386
408
2113
860
1447
469
497
476
503
30PAC
1447
Cooling
Seasonal efficiency
Indoor circuit
Expansion
vessel
Dimensions
Weight
ESEER
Nominal water flow
Pressure drop
Volume
Filled pressure
(m3/h)
(m.w.c)
l
kg/cm2
2,95
3,2
2,3
12
1,5
3,00
3,7
3,1
Length
Width
Height
Empty
In operation
mm
mm
mm
kg
kg
1117
860
1447
310
327
1398
860
1727
370
390
* Cooling capacity calculated in accordance with the EN-14511-2013 standard given for outlet water temperature conditions of 7ºC and 35ºC outdoor temperature.
** Total power input by compressor, motorised fan and electronic control under nominal conditions, calculated in accordance with the EN-14511-2013 standard. Options are
not included.
*** European Seasonal Energy Efficiency Ratio (ESEER) obtained in accordance with the calculation conditions established by the certification body EUROVENT.
**** Energy-efficient motors IE2.
***** Climatic warming potential of a kilogram of fluorinated greenhouse gas in relation to a kilogram of carbon dioxide over a period of 100 years.
74
C
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7