AHI Carrier Catalog | Page 730

Model
39SQP
Size
0405
0506
0606
0707
0808
0909
1010
Weight Unit without coils
kg
210
275
324
395
536
578
688
Unit with reheating and cooling coils
kg
277
360
423
518
712
783
923
Unit air flow Maximum
m 3 / s
0.68
1.04
1.25
1.70
2.22
2.81
3.47
m 3 / h
2450
3750
4500
6125
8000
10125
12500
Minimum
m 3 / s
0.20
0.34
0.43
0.62
0.91
1.25
1.48
m 3 / h
737
1225
1549
2247
3265
4501
5328
Unit thermal efficiency *
%
62
63
63
64
64
63
62
Unit external static pressure At max . air flow ( low static fan )
Pa
400
-
0
-
50
-
150
At max . air flow ( high static fan )
Pa
650
800
650
450
1300
550
1000
Specific unit fan power **
kW / m 3 / s 2.2
1.9
2.1
2
1.8
1.9
1.7
Unit sound data ***
Sound power level , casing radiated
dB ( A )
67
66
69
73
67
73
69
Sound power level , extract duct
dB ( A )
77
75
79
82
77
79
78
Sound power level , supply duct
dB ( A )
84
82
86
88
84
89
86
Heat reclaim heat exchanger
Cross-flow plate
Material
Aluminium
Capacity control
Bypass damper
Exhaust and supply fans Fan diameter
mm
225
280
280
315
400
400
500
Drive Rated motor power ( low static )
kW
1.1
1.1
1.5
2.2
2.2
2.2
4
Rated motor power ( high static )
kW
1.5
2.2
3
4
5.5
5.5
7.5
Exhaust and supply air filters
Pleated filter 100 mm , filter efficiency F7
Outside air pre-heating coil
Hot-water coil or electric heater ( option )
Supply air reheating coil
Hot-water coil or electric heater ( option )
Supply air cooling coil
Chilled-water coil ( option )
Control system
Digital control with web server
Chassis paint colour
Colour code : RAL 7035
*
Thermal efficiency of supply air at 2 m / s with the effect of supply air fan , outside air -10 ° C , extract air 22 ° C / 50 %.
**
Specific fan power with clean filters at 2 m / s and 200 Pa .
***
Sound power at 2 m / s and 200 Pa .
Note : Data for standard unit without optional coils and dampers .
AIR TREATMENT

Electrical data

Model 39
SQC 0405
SQC 0506
SQC 0606
SQR 0606
SQR 0707
SQR 0808
SQP 0405
SQP 0506
SQP 0606
SQP 0707
SQP 0808
Power circuit
Built-in main disconnect switch
Nominal power supply
V-ph-Hz 400-3-50 neutral
Voltage range
V
360-440
Maximum unit power
kW
3
4.77
6.37
6.37
8.75
11.75
Maximum supply cable size
mm 2
2.5
4
4
4
6
6
Main switch
A
25
25
25
25
40
40
Short circuit unit capacity
kA
15
15
15
15
15
15
Recommended power line fuse protection
A
20
25
25
25
35
35
Control circuit power
Built-in 24 V control transformer
Note : Electric pre-heater and reheater have separate power supply .
730 C A R R I E R 2 0 1 6 / 2 0 1 7