AIR TREATMENT MODULES 42GM
Physical data
42GM
Size 1.9 (2 pipes)
Size 1.9 (4 pipes)
Fan
Air flow
l/s (m3/h)
94 (337)
94 (337)
Pressure drop
Pa
290
290
Total cooling capacity
kW
2.20
2.20
Sensible cooling capacity
kW
1.70
1.70
Water flow rate
l/s (l/h)
0.11 (380)
0.11 (380)
Water pressure drop
kPa
65 (with 2-way valve)
47 (with 2-way valve)
Heating capacity
kW
-
2.21
Water flow rate
l/s
-
0.05 (190)
Water pressure drop
kPa
-
10
Low-capacity heating
W
470
-
High-capacity heating
W
1750
-
Sound power level (inlet and radiated)
dB(A)
65
65
Sound power level (outlet duct)
dB(A)
70
70
Sound pressure level*
dB(A)
49
49
Cooling mode
4-pipe heating mode
Electric heater
Sound levels
NR value
45
45
Power supply
V-ph-Hz
230-1-50
230-1-50
Power input
W
115
115
Current draw
A
0.81
0.81
Coil inlet/outlet diameters
in
1/2 gas
1/2 gas
Length
mm
1202
1202
Height
mm
412
412
Depth
mm
300
300
Weight
kg
30
30
AIR TREATMENT
Dimensions
Based on Eurovent rating standards:
Cooling: Entering/leaving air temperature = 27°C db/19°C wb – entering/leaving water temperature = 7°C/12°C.
Heating (2 pipes): Entering air temperature = 20°C – entering water temperature = 50°C, same water flow rate as in cooling.
Heating (4 pipes): Entering air temperature = 20°C – entering/leaving water temperature = 70°C/60°C.
* Based on a hypothetical sound attenuation for the room and the system of -21 dB(A).
Options/accessories
■■ Customised product on request
CONTROLS
35BD linear diffuser (supply and return air)
C
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7
683