AHI Carrier Catalog | Page 674

Main modules and components ■■ Variable-speed LEC fan motor assembly The 42BJ ICM LEC units are equipped with a variablespeed fan motor assembly controlled by a 0-10 V signal from the electronic Carrier controller. ■■ Water coil The water coil has aluminium fins mechanically bonded to copper tubes by expansion. Water inlet and outlet connections are threaded 1/2” gas. Air purge valves are standard. The coil is integral with the drain pan and the coil access door to ease removal for service. Coils available are: -- two-pipe coils with changeover or for use with an electric heater. -- four-pipe coils. ■■ Thermoformed condensate drain pan The main pan is below the coil with an auxiliary pan below the valves. This monobloc construction prevents leaks. With the coil on the suction side of the fan to facilitate drainage, condensate has to be drained through a nonreturn flap valve. The difference in height between the main and auxiliary drain pans is enough to overcome the depression within the unit and dispenses with the need for an in-built siphon. ■■ Constant volume fresh air controller (option) The ICM unit can be fitted with a constant fresh air flow controller allowing the number of air changes to be controlled accurately. It is vital to choose the correct constant fresh air flow controller for the intended occupancy of the room or zone. The following range of controllers is available: -- 8.3 l/s or 30 m3/h (-10%; +20%) -- 16.6 l/s or 60 m3/h (-10%; +20%) The fresh air supply is located upstream of the water coil. The collar which houses the flow controller is made of ABS and has the following diameter: 3 -- 125 mm for the controller with 16.6 l/s (60 m /h) 3 -- 74 mm for the controller with 8.3 l/s (30 m /h). The auxiliary pan is insulated. The drain stub itself has 16 mm external diameter. ■■ Filter and access The 42BJ ICM is fitted with a high-efficiency F5 or F6 type filter. Fire rating medium M1, metal frame Three filter access options are provided on the 42BJ: -- From above for units in false floor voids -- From below for units in false ceiling voids -- From the side (all applications) AIR TREATMENT MR60 MR75 MR85 MR90 MR100 MR105 MR110 MR120 MR130 MR140 MR160 43 2 1 12 3 4 B A 43 2 1 12 3 4 l/s m3/h A B 17 21 24 25 28 29 31 33 36 39 44 4-4 4-3 3-2 2-2 2-1 1-1 1-1 - 60 75 85 90 100 105 110 120 130 140 160 4-4 4-3 3-3 3-2 2-1 2-1 1-1 3-3 2-1 1-1 - Fresh air controller 674 C A R R I E R 2 0 1 6 / 2 0 1 7