INDIVIDUAL COMFORT MODULES 42BJ
Physical and electrical data
42BJ ICM LEC
1.9
Fan speed*
L
M
H
L
M
H
L
M
H
l/s
16
145
201
24
160
223
28
148
204
m3/h
56
521
722
88
575
803
101
534
733
Pa
1
50
97
1
50
99
3
50
92
Total cooling capacity
kW
0.45
2.99
3.74
0.66
3.95
5.26
1.12
3.94
4.91
Sensible cooling capacity
kW
0.36
2.34
3.00
0.46
2.91
3.95
0.75
2.78
3.53
Water flow rate
l/s
0.02
0.12
0.17
0.03
0.19
0.25
0.06
0.25
0.26
l/h
80
448
628
118
699
912
224
884
935
Water pressure drop
kPa
2
27
47
2
39
61
5
61
68
Water content
l
0.9
0.9
0.9
1.2
1.2
1.2
1.5
1.5
1.5
kW
0.51
3.56
4.45
0.75
4.72
6.33
1.19
4.53
5.77
Air flow
Available static pressure
2.9
4.9
Cooling mode**
Two-pipe heating mode***
Heating capacity
Four-pipe heating mode****
Heating capacity
kW
0.62
3.12
3.70
1.08
4.30
5.18
1.87
5.47
6.54
Water flow rate
l/s
0.02
0.07
0.10
0.03
0.10
0.12
0.05
0.15
0.16
l/h
60
267
348
94
376
449
168
550
577
Water pressure drop
kPa
1
15
23
4
32
41
8
67
73
Water content
l
0.2
0.2
0.2
0.29
0.29
0.29
0.45
0.45
0.45
Electric heater
V-ph-Hz
230-1-50
Maximum capacity
kW
0.5
1.9
2.23
0.75
2.12
2.25
1
2.25
2.25
Maximum current drawn
A
11
11
11
11
11
11
11
11
11
Sound power level (return + radiated)
dB(A)
29
53
59
34
52
59
32
56
61
Sound power level (supply)
dB(A)
26
59
66
20
63
69
31
65
72
Global sound power level
dB(A)
31
61
67
34
63
69
34
65
72
Sound pressure level†
dB(A)
10
40
46
13
42
48
13
44
51
NR value†
-
35
41
-
37
43
-
39
46
Electrical data, motor
230 V-1 ph-50 Hz, EC motor with low energy consumption
46
186
Sound levels
49
160
4
68
174
5
Power input
W
4
Air filter F5 or F6
mm
240 x 400
240 x 550
315 x 550
in
1/2
gas
1/2
gas
1/2
gas
Connection diameter, chilled and
hot-water coil
mm
200
200
250
mm
900
1100
1100
Depth
mm
665
815
815
Height
mm
270
270
345
Unit weight (standard)
kg
31
40
50
Fan speed: L = Low, M = Medium, H = High
Eurovent conditions: Entering air temperature 27°C/47% rh, entering water temperature 7°C, water temperature difference 5 K.
Eurovent conditions: Entering air temperature 20°C - entering water temperature 50°C, with same water flow rate as in cooling mode.
Eurovent conditions: Entering air temperature 20°C - entering water temperature 70°C, water temperature difference 10 K.