AHI Carrier Catalog | Page 650

Physical and electrical data at Eurovent conditions 42NH - Size 5
With G1 filter - without plenum
42NH 529 539 549
AIR TREATMENT
Fan speed 2V 5V 6V 8V 10V 2V 5V 6V 8V 10V 2V 5V 6V 8V 10V ( Eurovent certification speeds ) ( L ) ( M ) ( H ) ( Max ) ( L ) ( M ) ( H ) ( Max ) ( L ) ( M ) ( H ) ( Max ) Air flow l / s 96 213 244 307 347 96 213 244 307 347 96 213 244 307 347 m 3 / h 346 765 878 1105 1249 346 765 878 1105 1249 346 765 878 1105 1249 Available static pressure Pa 10 50 66 104 133 10 50 66 104 133 10 50 66 104 133 Cooling mode , two pipes * Total cooling capacity kW 1.90 3.63 4.01 4.69 5.08 2.03 4.43 4.97 5.88 6.35 Sensible cooling capacity kW 1.55 3.04 3.39 4.04 4.42 1.62 3.52 3.97 4.79 5.24 Water flow rate l / s 0.09 0.17 0.19 0.23 0.24 0.10 0.21 0.24 0.28 0.30 l / h 330 620 690 810 870 350 760 850 1010 1090 Water pressure drop kPa 8 27 32 42 48 8 37 46 61 69 Water content l 1.4 1.8
Heating mode , two pipes ** Heating capacity
kW
2.62
5.42
6.05
7.10
7.65
2.81
6.45
7.28
8.70
9.42
Cooling mode , four pipes *
Total cooling capacity
kW
1.86
3.70
4.10
4.80
5.19
1.96
4.09
4.59
5.51
6.02
Sensible cooling capacity
kW
1.51
3.06
3.42
4.07
4.45
1.58
3.33
3.76
4.57
5.04
Water flow rate
l / s
NA
0.09
0.18
0.19
0.23
0.25
0.09
0.19
0.22
0.26
0.29
l / h
320
640
700
820
890
340
700
790
950
1030
Water pressure drop
kPa
8
30
35
46
53
7
32
39
53
62
Water content
l
1.1
1.4
Heating mode , four pipes ***
Heating capacity
kW
2.40
4.47
4.91
5.65
6.04
2.61
5.54
6.13
7.03
7.44
Water flow rate
l / s l / h
NA
0.06
210
0.11
390
0.12
430
0.14
500
0.15
530
0.06
230
0.14
490
0.15
540
0.17
620
0.18
650
Water pressure drop
kPa
3
10
11
15
16
4
13
16
20
22
Water content
l
0.5
0.6
Electric heater
230V ± 10 % - 1ph
230V ± 10 % - 1ph
230V ± 10 % - 1ph
Maximum capacity
W
2000
2000
2000
Current drawn
A
9.1
9.1
9.1
Sound levels
Sound power level ( return and
dB ( A )
35
53
58
63
67
35
53
58
63
67
35
53
58
63
67
radiated )
Sound power level ( supply )
dB ( A )
36
57
61
66
70
36
57
61
66
70
36
57
61
66
70
Electrical data , motor Power input
W
9
52
78
146
212
9
52
78
146
212
9
52
78
146
212
Current drawn
A
0.12
0.67
0.95
1.58
1.88
0.12
0.67
0.95
1.58
1.88
0.12
0.67
0.95
1.58
1.88
FCEER [ energy class ] - 2 pipes
100
[ A ]
114
[ A ]
FCCOP [ energy class ]
150
[ A ]
170
[ A ]
FCEER [ energy class ] - 4 pipes
100
[ A ]
108
[ A ]
FCCOP [ energy class ]
131
[ A ]
152
[ A ]
Fan speed : L = Low , M = Medium , H = High
NA
*
Eurovent conditions : Entering air temperature = 27 ° C db / 47 % rh – entering water temperature = 7 ° C , water temperature difference = 5 K .
**
Eurovent conditions : Entering air temperature = 20 ° C , entering water temperature = 50 ° C , same water flow rate as in cooling .
***
Eurovent conditions : Entering air temperature = 20 ° C , entering water temperature = 70 ° C , water temperature difference = 10 K .
Eurovent certified data
650 C A R R I E R 2 0 1 6 / 2 0 1 7