AHI Carrier Catalog | Page 621

ROOM FAN COIL UNITS  42N Four-pipe coil 42N_, 4-pipe coil S15 Fan speed R1 Fan type S20 R2 R3 R4 R5 One, tangential Air flow R1 S26 R2 R3 R4 R5 One, centrifugal R1 R2 R3 One, centrifugal l/s 96 82 69 55 34 126 106 91 79 59 189 148 93 m3/h 345 296 247 198 123 453 382 327 283 214 681 534 334 Cooling mode* Total cooling capacity kW 1,46 1,3 1,15 1,04 0,75 2,04 1,89 1,65 1,47 1,19 2,7 2,29 1,67 Sensible cooling capacity kW 1,25 1,13 0,98 0,86 0,6 1,71 1,55 1,35 1,19 0,96 2,34 1,94 1,37 Water flow rate l/s 0,07 0,06 0,06 0,05 0,04 0,1 0,09 0,08 0,07 0,06 0,13 0,11 0,08 l/h 250 220 200 180 130 350 320 280 250 210 460 390 290 m3/h 0,25 0,22 0,2 0,18 0,13 0,35 0,32 0,28 0,25 0,21 0,46 0,39 0,29 14 11 9 5 5 5 4 3 2 8 5 3 Water pressure drop kPa 17 Water content l 0.6 Heating capacity kW 1,44 1,29 1,15 0,95 0,58 2,89 2,59 2,41 2,23 1,81 3,76 3,21 2,49 Water flow rate l/s 0,04 0,03 0,03 0,02 0,01 0,07 0,06 0,06 0,06 0,04 0,09 0,08 0,06 l/h 130 110 100 80 50 250 230 210 200 160 330 280 220 1.1 1.1 Heating mode** m /h 0,13 0,11 0,1 0,08 0,05 0,25 0,23 0,21 0,2 0,16 0,33 0,28 0,22 Water pressure drop kPa 3 2 2 1 1 10 8 7 6 4 15 11 7 Water content l 0.2 Sound power level dB(A) 52 47 43 37 29 52 46 43 37 32 61 54 44 Sound pressure level*** dB(A) 43 38 34 28 20 43 37 34 28 23 52 45 35 39 34 29 23 16 36 32 29 22 15 47 40 31 3 0.3 0.3 Sound levels NR Value Electrical data W 30 23 19 17 16 36 34 31 30 29 45 55 65 Current drawn A 0.13 0.11 0.09 0.08 0.08 0.16 0.15 0.14 0.13 0.12 0.3 0.25 0.2 Eurovent energy class FCEER/FCCOP E/E E/E E/E AIR TREATMENT Power input Connection diameter Cooling in 3/4 gas 3/4 gas 3/4 gas Heating in 1/2 gas 1/2 gas 1/2 gas Eurovent conditions: Entering air temperature = 27°C db/19°C wb – entering/leaving water temperature = 7°C/12°C, high fan speed. Eurovent conditions: Entering air temperature = 20°C, entering water temperature = 50°C, same water flow rate as in cooling mode. Based on a hypothetical acoustic attenuation for the room and the air distribution system of -9 dB(A). This unit complies with all applicable standards for EC marking (for further details see Declaration of Conformity). Except the unit size 42N_S65 which is not CE labeled due to fan ­efficiency ­regulation 327/2011 but is fully compliant with Machinery (2006/42/EC) and Electromagnetic Compatibility (2004/108/EC) directives. CONTROLS * ** *** † C A R R I E R 2 0 1 6 / 2 0 1 7 621