ONE-WAY COANDA EFFECT CASSETTE 42KY
Technical features
Electrical specifications of the motors
42KY
Input power
W
Input amps
A
Motor information
AC asynchronous motor
10
20
30
LEC motor
19
29
39
V5
V4
V3
V2
V1
V5
V4
V3
V2
V1
70
45
41
38
34
0,30
0,21
0,19
0,18
0,17
38
17
12
8
5
0,18
0,09
0,07
0,04
0,02
56
38
21
15
11
0,40
0,28
0,17
0,13
0,10
70
45
41
38
34
0,30
0,21
0,19
0,18
0,17
101
77
56
47
40
0,32
0,29
0,24
0,22
0,21
38
17
12
8
5
0,18
0,09
0,07
0,04
0,02
Motor operating range: Min recovery T°C: +5°C
Max recovery T°C: 40°C
Electrical heater specifications - Input voltage 230V - 1 ph - 50Hz
42KY cassette
10/19
20/29
30/39
Electrical power
W
-
900
1200
Input amps
A
-
3.6
4.8
Options (Factory Assembled)
Name
Condensate drain pump
Lift kit
Frame for 675 x 675 suspended ceiling tiles
Finishing trim frame for STAFF ceilings.
Water coil with protected fins
Name
Condensate drain pump kit
Elastic dampers (4 per device)
Lift kit
Self adjusting module diameter 100 mm
15/30/45 m3/h
60/75/90 m3/h
AN adapter kit Diameter 100/125 mm
Frame kit for suspended ceiling 675x675
LEC motor speed control 3 speed ON/OFF unit kit (only for thermostat or controllers not from CARRIER that have 3 230V speed outputs)
AIR TREATMENT
Accessories (Available separately)
C
A
R
42KY cassette
Operating pressure
max. 16 Bar
Indoor temperature
-
Electrical supply
Nominal usage limitations
R
I
E
R
2
0
1
6
/
2
0
1
7
Minimum water inlet temperature: 6°C
Maximum water inlet temperature:
4 Tubes: 80°C
2 Tubes: 70°c
2 Tubes + electric: 55°C (min air flow 200m3/h)
Minimum temperature: 5°C
Maximum temperature: 40°C
Min 207 - Max 253 V for units without electrical heater
Min 216 - Max 244 V for units with electrical heater
615
CONTROLS
Limitations of use