WATER-COOLED SCREW CHILLERS  30XWH 254-1762 Physical data, units for high condensing temperatures 254 304 354 402 452 552 Heating application as per EN14511-3:2013† - unit with option 150 Condition 2 Nominal heating capacity kW 325 362 408 478 506 566 COP kW/kW 4.62 4.59 4.55 4.29 4.50 4.43 Eurovent class heating A A A B A B Heating application †† - unit with option 150 Condition 2 Nominal heating capacity kW 324 361 407 476 504 564 COP kW/kW 4.85 4.81 4.78 4.46 4.70 4.66 Sound levels - unit with option 150 Sound power level* dB(A) 95 95 95 99 99 99 Sound pressure level at 1 m** dB(A) 78 78 78 82 82 82 Sound levels - unit with option 257*** Sound power level* dB(A) 96 96 96 Sound pressure level at 1 m** dB(A) 78 78 78 Dimensions - unit with optio n 150 Length mm 2724 2724 2724 2741 2741 2741 Width mm 928 928 928 936 936 936 Height mm 1567 1567 1567 1692 1692 1692 Operating weight**** kg 2017 2036 2072 2575 2575 2613 Compressors Semi-hermetic 06T screw compressors, 50 r/s Circuit A 1 1 1 1 1 1 Circuit B Refrigerant**** - standard unit Circuit A kg 84 80 78 82 82 82 Circuit B kg Global Warming Potential (GWP) tonnes 120 114 112 117 117 117 Tonnes of equivalent CO2 of greatest circuit Capacity control Touch Pilot, electronic expansion valves (EXV) Minimum capcity % 30 30 30 30 30 30 Evaporator Multi-pipe flooded type Water volume l 50 56 61 70 70 70 Water connections (Victaulic) in 5 5 5 5 5 5 Drain and vent connections (NPT) in 3/8 3/8 3/8 3/8 3/8 3/8 Max. water-side operating pressure kPa 1000 1000 1000 1000 1000 1000 Condenser Multi-pipe flooded type Water volume l 55 55 55 76 76 76 Water connections (Victaulic) in 5 5 5 5 5 5 Drain and vent connections (NPT) in 3/8 3/8 3/8 3/8 3/8 3/8 Max. water-side operating pressure kPa 1000 1000 1000 1000 1000 1000 602 652 702 802 606 4.54 A 716 4.45 A 789 4.45 A 829 4.41 A 603 4.82 713 4.66 786 4.70 826 4.68 99 82 102 84 102 84 102 82 96 78 100 82 100 82 100 82 2741 936 1692 2644 3059 1090 1858 3407 3059 1090 1858 3438 3059 1090 1858 3462 1 - 1 - 1 - 1 - 82 - 145 - 140 - 135 - 117 207 200 193 30 15 15 15 70 5 3/8 1000 109 6 3/8 1000 109 6 3/8 1000 109 6 3/8 1000 76 5 3/8 1000 109 6 3/8 1000 109 6 3/8 1000 109 6 3/8 1000 CONTROLS † Eurovent-certified performances in accordance with standard EN14511-3:2013. † † Gross performances, not in accordance with EN14511-3:2013. These performances do not take into account the correction for the proportional heating capacity and power input generated by the water pump to overcome the internal pressure drop in the heat exchanger. Conditions in cooling mode: evaporator entering/leaving water temperature 12°C/7°C, condenser entering/leaving water temperature 30°C/35°C, evaporator and condenser fouling factor = 0 m2 K/W. Conditions in heating mode: condenser entering/leaving water temperature 40°C/45°C, evaporator entering/leaving water temperature 10°C/7°C, evaporator and condenser fouling factor = 0 m2 K/W. * In dB ref=10-12 W, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). Measured in accordance with SO 9614-1 and certified by Eurovent. ** In dB ref 20µPa, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). For information, calculated from the sound power level Lw(A). *** Option 257 = Low noise level. **** Weight shown is guideline only. Please refer to the unit nameplate. Eurovent certified data C A R R I E AIR TREATMENT 30XWH- HEATING High-efficiency units (option 150) R 2 0 1 6 / 2 0 1 7 543