AHI Carrier Catalog | Page 525

WATER-SOURCE HEAT PUMPS  61WG 020-090 Remote control option Pro-Dialog+ permits control and monitoring of the unit using a wired interface: -- Start/stop -- Operating mode selection: cooling or heating -- Demand limit -- Dual setpoint -- User safety loop. The control remotely reports any problem. The CCN clock board connection offers other control possibilities: Two indepen dent time schedules to control: -- Unit start/stop -- Operation at a second chilled-water setpoint (for example: unoccupied mode) -- Operation of two units in parallel (master/slave function), and remote control via a communication bus (RS 485 serial port). Minimum Maximum Evaporator Entering water temperature at start-up °C 7.5* 27 Leaving water temperature during operation °C 5** 20 2.5 7 Entering/leaving water temperature difference K Condenser Entering water temperature at start-up °C 15*** 60**** Leaving water temperature during operation °C 20 65 2.5 18 Entering/leaving water temperature difference K * ** For entering water temperatures below 7.5 °C at start-up, contact Carrier. If the leaving water temperature is below 5 °C, a frost protection solution must be used. Please refer to option 6 for evaporator leaving water low-temperature applications (< 5 °C). *** For applications with a condenser entering temperature below 15 °C the use of a three-way valve is recommended. This three-way valve can be controlled by the 0-10 V analogue output of the Pro-Dialog+ control. **** For a water flow rate that corresponds to a maximum water-side temperature difference of 5 K. 61WG + option 272 (geothermal application) 65 60 55 50 45 40 35 30 25 20 15 Standard Option 272 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 20 Evaporator leaving water temperature, °C 61WG standard unit 61WG unit with option 272 (brine to water) Option 272: Condenser-side high-temperature water production, with glycol solution on the evaporator side HEATING 61WG Condenser leaving water temperature, °C Operating limits Minimum Maximum Evaporator Entering water temperature at start-up °C -2.5* 25 Leaving water temperature during operation °C -5* 20 Entering/leaving water temperature difference K 2.5 5 Entering water temperature at start-up °C 15** 60*** Leaving water temperature during operation °C 20 65 2.5 18 Entering/leaving water temperature difference K * ** A frost protection solution must be used. For applications with a condenser entering temperature below 15 °C the use of a three-way valve is recommended. This three-way valve can be controlled by the 0-10 V analogue output of the Pro-Dialog+ control. For a water flow rate that corresponds to a maximum water-side temperature difference of 5 K. CONTROLS *** AIR TREATMENT Condenser C A R R I E R 2 0 1 6 / 2 0 1 7 525