Hydronic module ( options 116T , 270T )

Typical water piping diagram
2
Unit water inlet
1
3
6
PT
7
4
5
TT
9
15
Components of unit and hydronic module
Condenser water loop ( 61WG )
Unit water outlet 2
1 PT
Unit water inlet 7
6
3
Evaporator water loop ( 61WG )
TT
10
4
PT
8
5
6
TT
9
14
13 16
1 Victaulic screen filter ( option 293 or 293A only ) 2 Expansion tank ( option 293 or 293A only ) 3 Safety valve ( option 293 or 293A only ) 4 Water pump 5 Air vent 6 Water drain valve 7 / 8 Entering / leaving pressure sensor 9 / 10 Entering / leaving temperature probe 12 Flow switch 61WG option 272 ( sizes 020-045 only ) 13 Compressor 14 Evaporator 15 Condenser 16 Expansion device
Note : Units without hydronic module include a flow switch .
Unit water outlet
TT
PT
12
10
8
6
Physical data , units with hydronic module
HEATING
61WG 020 025 030 035 040 045 050 060 070 080 090
Operating weight , 61WG ( options 116V and 270V )*
kg
305
313
313
321
327
334
513
521
533
544
574
Height **
mm
1463
1463
1463
1463
1463
1463
1463
1463
1463
1463
1463
Hydronic module Maximum operating pressure
kPa
300
300
300
300
300
300
300
300
300
300
300
Water filter ( max . removed particle diameter )
mm
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
Expansion tank capacity ***
l
8
8
8
8
8
8
12
12
12
12
12
Water connections
in
1.5
1.5
1.5
1.5
1.5
1.5
2
2
2
2
2
* Weight shown is a guideline only . ** The length and width dimensions are the same as for the standard unit . *** When delivered , the standard pre-inflation of the tanks is not necessary the optimal value for the system . To permit changing the water volume , change the inflation pressure to a pressure that is close to the static head of the system . Fill the system with water ( purging the air ) to a pressure value that is 10 to 20 kPa higher than the pressure in the tank .
Electrical data , options 116T , 270T
The original pumps that are factory-installed in these units have motors with efficiency class IE2 . The additional electrical data required by regulation 640 / 2009 are given in the installation , operation and maintenance instructions .
This regulation regards the application of directive 2005 / 32 / CE on the eco-design requirements for electric motors .
Pump curve , 61WG ( options 116 , 270 )
Data applicable for : --
Fresh water 20 ° C
--
In case of use of the glycol , the maximum water flow is reduced
Pressure head , kPa
518
1
Fixed-speed low-pressure pumps ( options 116T - 270T )
2
Water flow rate , l / s 1 61WG-020-080 2 61WG 090
Pressure head , kPa
--
The curves represented below are in normal conditions :
-- leaving water on the back side of the unit ( without option 274 ).
Variable-speed high-pressure pumps ( options 116V - 270V )
220 200 180 4 160 140 3 120 100 80 60 40 20 0
0 1 2 3 4 5 6 7 8 9 10 11 12
Water flow rate , l / s 3 61WG 020-045 4 61WG 050-090
C A R R I E R 2 0 1 6 / 2 0 1 7