AIR-TO-WATER HEAT PUMP WITH INTEGRATED
HYDRONIC MODULE 30RQM/30RQP 160-520
Features and advantages
■■ Greenspeed® variable-speed pump to reduce pumping
energy use up to 2/3 (option recommended by Carrier):
-- Elimination of the energy losses caused by the water
flow control valve by the electronic setting of the
nominal water flow
-- Energy savings during stand-by periods or part-load
operation by automatic water pump speed reduction.
Pump motor energy use varies as the cube of the
speed so that only 40% speed reduction can reduce
energy consumption by 80%
-- Improved unit part-load performance (Increased
SCOP and SEER values with variable water flow
following EN14825).
Refer to hydronic option chapter for more information.
■■ Extra energy savings through partial heat recovery option
that permits free hot water production.
■■ Reduced maintenance costs
-- Fast diagnosis of possible incidents and their history
via the control
-- R-410A refrigerant is easier to use than other
refrigerant blends.
CONTROLS
AIR TREATMENT
■■ High unit full and part load energy efficiency and efficient
design of the water side:
-- Standardised Eurovent values in accordance with EN
14511-3:2013 EER up to 2.9 and ESEER up to 4.35
(30RQP version)
-- 30RQP and 30RQM ranges are compliant with EU
Eco-design Tier 1 Minimum Efficiency Performance
Standards (MEPS) in heating that apply from
September 2015
-- 30RQP range and 30RQM sizes 430-470-520 are
compliant with EU Eco-design Tier 2 MEPS in heating
that apply from September 2017
-- Multiple scroll compressors equipped with a
high-efficiency motor that permit exact matching of
the capacity to the load
-- Electronic expansion device permitting operation at a
lower condensing pressure and improved utilisation
of the evaporator heat exchange surface (superheat
control)
-- Air heat exchanger with Greenspeed® variable speed
fans (30RQP version)
-- Low pressure drop brazed plate heat exchangers
(pressure drops < 45 kPa at Eurovent conditions).
■■ Specific control functions to reduce unit energy use
during occupied and unoccupied periods:
-- Internal time schedules clock: Permits heat pump
on/off control and operation at a second set point
-- Automatic water set-point offset based on outside air
temperature or room air temperature via an option
-- Floating high-pressure management
-- Variable-speed fan control
-- Cooling and heating demand limitation.
Refer to control chapter for more information.