AHI Carrier Catalog | Page 490

Air pressure drop

Selection of a ductable unit
The 30RQSY ranges are designed for indoor installation in a plant room . For this type of installation the cold or hot air leaving the air-cooled air heat exchangers is discharged by the fans to the outside of the building , using a duct system .
Selection based on the pressure drop
The cooling and heating capacities are given for an available pressure of 160 Pa and for a unit without filter .
HEATING
The units are equipped with fans with available pressure , designed to operate with air discharge ducts with maximum pressure drops of 180 Pa or 240 Pa on certain sizes .
To compensate for these pressure drops this range of ductable units equipped with variable-speed fans with a maximum speed of 19 r / s .
In the cooling mode , the full-load or part-load speed is controlled by a patented algorithm that permanently optimises the condensing temperature to ensure the best unit energy efficiency ( EER ) whatever the operating conditions and pressure drops of the system ductwork .
In the heating mode , the full-load or part-load speed of each circuit is fixed and at the configured maximum ( range configurable from 12 r / s to 19 r / s ) based on the constraints and characteristics of the installation site . The maximum configured speed applies to both the heating and cooling mode .
Each refrigerant circuit ( A and B ) must have a separate ducting system to prevent any air recycling between the air heat exchangers of the different refrigerant circuits .
To collect the defrost water from the coils in the heating mode , 30RQSY units must be installed on an appropriate surface to permit efficient condensate drainage and evacuation and to p revent any risk of flooding at the site . A condensate collection pan is available for 30RQSY 039- 078 units .
To calculate the performances at other pressure drops please use the correction factors below .
Cooling mode
30RQSY 039-050 / 30RQSY 080-120
Duct pressure drop
Fan speed , r / s
Power input coefficient
Cooling capacity coefficient
0
12.00
0.943
1.019
50
13.33
0.962
1.012
100
14.66
0.980
1.006
130
15.46
0.990
1.003
160
16.26
1.000
1.000
200
17.31
1.012
0.998
240
18.36
1.023
0.996
30RQSY 060-078 / 30RQSY 140-160
Duct pressure drop
Fan speed , r / s
Power input coefficient
Cooling capacity coefficient
0
15.83
0.929
1.018
50
16.81
0.944
1.016
100
17.78
0.964
1.014
130
18.36
0.978
1.011
160
18.36
1.000
1.000
180
18.36
1.019
0.991
Heating mode
30RQSY 080-120
Duct pressure drop
Fan speed , r / s
Power input coefficient
Heating capacity coefficient
0
18.36
0.990
1.016
50
18.36
0.990
1.012
100
18.36
0.990
1.009
130
18.36
1.000
1.005
160
18.36
1.000
1.000
200
18.36
1.000
0.994
240
18.36
1.010
0.981
30RQSY 140-160
Duct pressure drop
Fan speed , r / s
Power input coefficient
Heating capacity coefficient
0
18.36
1.000
1.026
50
18.36
1.000
1.020
100
18.36
1.000
1.011
130
18.36
1.000
1.007
160
18.36
1.000
1.000
180
18.36
1.001
0.993
Note : Pressure drop , clean filter = 6 Pa Pressure drop , dirty filter = 12 Pa
490