DUCTABLE AIR-TO-WATER HEAT PUMPS 30RQSY 039-160
Physical data
30RQSY
039
045
050
060
070
078
080
090
100
120
140
160
Cooling
Full load
C1
Nominal capacity
kW
37.2
43.5
49.8
57.6
62.6
72.6
77.7
85.6
95.9
113.2
129.6
147.1
performances*
C1
EER
kW/kW
2.85
2.76
2.7
2.76
2.7
2.55
2.78
2.71
2.7
2.71
2.74
2.54
C1
Eurovent Energy Class
A
A
A
A
A
B
A
A
A
A
A
B
C2
Nominal capacity
kW
46.5
54.4
63.2
70.1
77.5
91.5
97.4
107.9
117.7
143.2
160.3
183.6
C2
EER
kW/kW
3.29
3.23
3.14
3.11
3.07
2.9.3
3.18
3.15
3.11
3.12
3.13
2.88
ESEER
kW/kW
3.84
3.9
3.85
3.77
3.73
3.66
3.73
3.65
3.77
4
3.82
3.75
H1
Nominal capacity
kW
42.7
46.9
54.6
63.2
71.7
80.1
82.5
94.9
103
120.7
141.9
163
H1
COP
kW/kW
3.68
3.69
3.69
3.8
3.7
3.63
3.77
3.73
3.65
3.64
3.74
3.57
H1
Eurovent Energy Class
C
C
C
B
C
D
B
C
D
C
C
D
H2
Nominal capacity
kW
41.8
46.7
53.4
61.7
70
78
79.6
92.8
100.9
116.9
138.6
158.8
H2
COP
kW/kW
3.06
3.04
3
3.07
3.09
3
3.11
3.04
3
3
3.07
2.95
H2
Eurovent Energy Class
A
A
A
A
A
A
A
A
A
A
A
B
H1
Energy Class
A
A
A
A
A+
A
A
-
-
-
-
-
H1
SCOP
kW/kW
2.98
3.01
2.98
3.1
3.12
3.07
3.05
3
2.99
3.05
3.17
3.12
H1
Ƞs heat
%
116
117
116
121
122
120
119
117
117
119
124
122
Prated
KW
33
37
42
51
58
65
66
77
84
96
114
132
84
84
84
87
87
87
87
87
87
87
90
90
kg
507
514
548
562
562
569
748
916
925
983
1078
1095
Single high-pressure pump
kg
522
529
563
577
577
584
735
904
913
975
1074
1090
Dual high-pressure pump
kg
548
555
589
602
603
610
761
949
958
1024
1111
1128
2/-
2/-
3/-
3/-
3/-
2/2
2/2
Seasonal
Efficiency*
Full load
performances*
Seasonal
Efficiency**
Sound Power Level Standard Unit (Radiated) dB(A)
HEATING
Heating
ESP = 80 Pa
Operating weight†
Standard unit without hydronic module
Compressor
Hermetic scroll compressors. 48.3 r/s
Circuit A/B
2/-
Refrigerant
R-410A
Capacity control
Touch Pilot Junior
Air heat exchangers
Grooved copper tubes and aluminium fins
Fans
Axial Flying Bird IV with rotating shroud
Quantity
1
1
1
1
1
1
2
2
2
2
2
2
3692
3690
3910
5278
4982
5267
7770
7380
7376
7818
9964
10534
Total air flow (at high speed)
l/s
2/-
2/-
2/-
2/-
Water heat exchanger
Direct expansion, plate heat exchanger
Hydronic module (option)
Single or dual pump, Victaulic screen filter, safety valve, expansion tank, purge valves (water and air),
AIR TREATMENT
Standard unit with hydronic module
pressure sensors
Dimensions
††
mm
2100
2150
2275
Depth
mm
1140
1140
2125
Height
mm
1380
1380
1380
Cooling mode conditions: Water heat exchanger, entering/leaving temperature 12°C/7°C, fouling factor 0 m2 K/W. Outside air temperature 35°C
Cooling mode conditions::Water heat exchanger, entering/leaving temperature 23°C/18°C, fouling factor 0 m2 K/W. Outside air temperature 35°C
Heating mode conditions: Water heat exchanger water entering/leaving temperature 30°C/35°C, fouling factor 0 m2 K/W. Outside air temperature 7°C db/6°C wb,
Heating mode conditions: Water heat exchanger water entering/leaving temperature 40°C/45°C, fouling factor 0 m2 K/W. Outside air temperature 7°C db/6°C wb,
In accordance with standard EN14511-3:2013
In accordance with standard EN14825:2013, average climate
Weight shown is a guideline only.
The value is for units without filter frame.
Eurovent certified data
C
A
R
R
I
E
CONTROLS
C1
C2
H1
H2
*
**
†
††
Length
Eurovent certified data
R
2
0
1
6
/
2
0
1
7
481