REVERSIBLE AIR-TO-WATER HEAT PUMPS 30RQS 039-160
Physical data
30RQS
039
045
050
060
070
078
080
090
100
120
140
160
Cooling
Full load
C1
Nominal capacity
kW
38
43.5
49.8
58.5
63.6
73.7
77.7
85.6
95.9
113.2
131.6
149.4
performances*
C1
EER
kW/kW
2.84
2.70
2.65
2.77
2.70
2.58
2.79
2.70
2.70
2.69
2.77
2.58
C1
Eurovent Energy Class
C
C
D
C
C
D
C
C
C
D
C
D
C2
Nominal capacity
kW
47.5
54.4
63.2
71.3
78.9
93
97.4
107.9
117.7
143.2
163.1
186.8
C2
EER
kW/kW
3.28
3.16
3.09
3.12
3.08
2.97
3.19
3.14
3.1
3.1
3.17
2.92
ESEER
kW/kW
3.80
3.77
3.81
3.61
3.61
3.57
3.84
3.77
3.88
4.04
3.75
3.67
H1
Nominal capacity
kW
42.7
46.9
54.5
63.0
71.4
79.7
82.5
95.0
103.0
120.9
141.3
162.2
H1
COP
kW/kW
3.72
3.72
3.76
3.73
3.72
3.47
3.74
3.74
3.77
3.73
3.73
3.59
H1
Eurovent Energy Class
D
D
C
D
D
E
D
D
C
D
D
E
H2
Nominal capacity
kW
41.8
46.7
53.4
61.4
69.6
77.5
79.7
92.8
100.9
116.9
137.8
157.9
H2
COP
kW/kW
3.08
3.05
3.03
3.03
3.06
2.87
3.08
3.02
3.09
3.06
3.07
2.97
H2
Eurovent Energy Class
B
B
B
B
B
C
B
B
B
B
B
C
H1
Energy Class
A
A
A+
A
A
A
A
-
-
-
-
-
H1
SCOP
kW/kW
3.07
3.1
3.21
3.07
3.1
2.96
3.14
3.17
3.23
3.23
3.14
3.13
H1
Ƞs heat
%
120
121
125
120
121
115
123
124
126
126
123
122
Prated
KW
33
37
42
51
57
65
66
76
83
97
113
131
dB(A)
80
81
81
86
87
87
84
84
84
84
90
90
kg
506
513
539
552
553
560
748
895
903
959
1060
1078
Single high-pressure pump
kg
535
543
569
582
582
590
778
927
935
995
1099
1117
Dual high-pressure pump
kg
561
569
594
608
608
616
804
972
980
1043
1136
1127
2/-
2/-
3/-
3/-
3/-
2/2
2/2
Seasonal
Efficiency*
Full load
performances*
Seasonal
Efficiency**
Sound Power Level Standard Unit
HEATING
Heating
Operating weight†
Standard unit without hydronic module
Compressor
Hermetic scroll compressors, 48.3 r/s
Circuit A/B
2/-
Refrigerant
R-410A
Capacity control
Touch Pilot Junior
Air heat exchangers
Grooved copper tubes and aluminium fins
Fans
Axial Flying Bird IV with rotating shroud
Quantity
Total air flow (at high speed)
l/s
2/-
2/-
2/-
2/-
1
1
1
1
1
1
2
2
2
2
2
2
3800
3800
3800
5300
5300
5300
7600
7600
7600
7600
10600
10600
Water heat exchanger
Direct expansion, plate heat exchanger
Hydronic module (option)
Single or dual pump, Victaulic screen filter, safety valve, expansion tank, purge valves (water and air),
pressure sensors
AIR TREATMENT
Standard unit with hydronic module
Dimensions
mm
1090
2273
mm
2109
2136
Height
mm
1330
1330
Cooling mode conditions: Water heat exchanger, entering/leaving temperature 12°C/7°C, fouling factor 0 m K/W. Outside air temperature 35°C
Cooling mode conditions::Water heat exchanger, entering/leaving temperature 23°C/18°C, fouling factor 0 m2 K/W. Outside air temperature 35°C
Heating mode conditions: Water heat exchanger water entering/leaving temperature 30°C/35°C, fouling factor 0 m2 K/W. Outside air temperature 7°C db/6°C wb,
Heating mode conditions: Water heat exchanger water entering/leaving temperature 40°C/45°C, fouling factor 0 m2 K/W. Outside air temperature 7°C db/6°C wb,
In accordance with standard EN14511-3:2013
In accordance with standard EN14825:2013, average climate
Weight shown is a guideline only.
2
CONTROLS
C1
C2
H1
H2
*
**
†
Length
Depth
Eurovent certified data
Eurovent certified data
C
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7
467