Net cooling capacity * |
kW |
18,40 |
21,00 |
25,50 |
31,40 |
35,70 |
Net power input *** |
kW |
7,20 |
7,95 |
9,10 |
11,50 |
13,60 |
Net efficiency |
EER |
2,55 |
2,64 |
2,81 |
2,74 |
2,62 |
Seasonal efficiency |
ESEER **** |
2,89 |
2,99 |
3,20 |
3,14 |
3,03 |
Net heating capacity ** |
kW |
21,40 |
23,90 |
29,30 |
36,40 |
42,50 |
Net power input *** |
kW |
7,10 |
7,90 |
9,50 |
11,90 |
13,90 |
Net efficiency |
COP |
3,03 |
3,03 |
3,08 |
3,05 |
3,05 |
SCOP |
3,07 |
2,95 |
3,29 |
3,28 |
3,18 |
ŋs Heat |
120 % |
115 % |
133 % |
128 % |
124 % |
Prated |
17,79 |
19,81 |
24,50 |
29,84 |
34,40 |
SCOP |
3,41 |
3,58 |
3,82 |
3,67 |
3,65 |
ŋs Heat |
134 % |
140 % |
150 % |
144 % |
143 % |
Prated |
13,09 |
14,68 |
18,01 |
22,41 |
25,89 |
Nominal air flow |
( m 3 / h ) |
6500 |
7000 |
10000 |
12200 |
14000 |
Nominal available static pressure |
( mm . w . c ) 20 |
|||||
Maximum available static pressure |
( mm . w . c ) 63,7 |
70,3 |
45,6 |
65,1 |
62,7 |
|
Number / diameter |
1 / 500 |
1 / 560 |
2 / 560 |
|||
Motor output |
kW |
2,7 |
2,8 |
3,0 |
2 x 3,0 |
|
Power input **** |
kW |
1,33 |
1,21 |
1,87 |
2,20 |
2,52 |
Speed |
( r . p . m .) |
1700 |
1780 |
1500 |
1500 |
|
Nominal water flow |
( m 3 / h ) |
3,2 |
3,7 |
4,5 |
5,4 |
6,2 |
Pressure drop |
( m . w . c ) |
1,6 |
2,1 |
1,6 |
2,4 |
3,1 |
Minimum water flow |
( m 3 / h ) |
2,5 |
2,9 |
3,4 |
4,1 |
4,6 |
Maximum water flow |
( m 3 / h ) |
6,6 |
7,4 |
9,1 |
11,3 |
12,8 |
Type of hydraulic connections |
Rosca gas |
|||||
Diameter of connections |
1 1 / 4 ” M |
1 1 / 2 ” M |
Compressor |
Type |
Scroll |
|||||
Number of compressors / stages / circuits |
1 |
||||||
Oil type |
Copeland 3MAF 32 cST , Danfoss POE 160 SZ , ICI Emkarate RL 32 CF , Mobil EAL Artic 22 CC |
||||||
Volume of oil |
l |
3,0 |
3,3 |
3,3 |
3,3 |
6,2 |
|
Refrigerant |
Type |
R-410A |
|||||
Global warming potential ( GWP ) ******* |
2.088 |
||||||
Charge |
kg |
6,0 |
6,3 |
6,8 |
8,9 |
9,2 |
|
Environment impact |
( tCO 2 e ) |
12,5 |
13,2 |
14,2 |
18,6 |
19,2 |
Electrical power supply |
400 V / III ph / 50 Hz (± 10 %) |
Power supply |
3 Hilos + Tierra + Neutro |
Compressor |
A |
15,2 |
17,3 |
20,5 |
25,4 |
30,5 |
Fan |
A |
4,2 |
4,3 |
4,6 |
9,2 |
9,2 |
Control |
A |
0,9 |
0,9 |
0,9 |
0,9 |
0,9 |
Total |
A |
20,3 |
22,5 |
26,0 |
35,5 |
40,6 |
Dimensions |
Length |
mm |
1117 |
1398 |
2113 |
|||
Width |
mm |
860 |
860 |
860 |
||||
Height |
mm |
1447 |
1727 |
1447 |
||||
Weight |
Empty |
kg |
294 |
351 |
368 |
450 |
455 |
|
In operation |
kg |
298 |
358 |
376 |
465 |
468 |
||
*
**
***
|
Cooling capacity calculated in accordance with the EN-14511-2013 standard given for outlet water temperature conditions of 7 º C and 35 º C outdoor temperature .
Heating capacity calculated in accordance with the EN-14511-2013 standard given for outlet water temperature conditions of 45 º C and 6 º C WB outdoor temperature .
Total power input by compressor , motorised fan and electronic control under nominal conditions , calculated in accordance with the EN-14511-2013 standard .
|
|||||||
****
*****
|
Options are not included .
European Seasonal Energy Efficiency Ratio ( ESEER ) obtained in accordance with the calculation conditions established by the certification body EUROVENT .
Values calculated in accordance with the EN-14825-2013 standard given for bivalente temperature of -5 º C in average climate and 2 º C in warmer climate .
|
|||||||
******
Energy-efficient motors IE2 .
******* Climatic warming potential of a kilogram of fluorinated greenhouse gas in relation to a kilogram of carbon dioxide over a period of 100 years .
|