Electrical data
30RQ
017
021
026
033
040
Power circuit
Nominal power supply
V-ph-Hz
Control circuit supply
*
**
***
400-3-50 ± 10%
24 V via internal transformer
Maximum start-up current (Un)*
A
75
95
118
118
176
Maximum operating power input**
kW
7.8
9.1
11
13.8
17.5
Nominal unit operating current draw***
A
8
12
16
17
25
Maximum instantaneous start-up current (locked rotor current of the compressor).
Power input, compressors and fans, at the unit operating limits (saturated suction temperature 10°C, saturated condensing temperature 65°C) and nominal voltage of 400 V
(data given on the unit nameplate).
Standardised Eurovent conditions: water heat exchanger entering/leaving water temperature 12°C/7°C, outside air temperature 35°C.
Type key
30R Q
-
021
C
H
E
-
B
-
-
Revision status
Product Range
New option (not used)
HEATING
Q - Heat pump AquaSnap
- - Standard
A - Remote User Interface HMI
Standard version
-
B
C
D
Nominal capacity
C - Power supply with neutral cable (not available for size 40)
D - Power supply without neutral cable
- Without gateway
- CCN Jbus gateway
- CCN Bacnet gateway
- CCN LONtalk gateway
Standard
0
H
F
R
Z
- Without hydronic module
- With hydronic module with expansion tank
- With hydronic module with expansion tank and water filling system
- With hydronic module, without expansion tank
- With hydronic module, w/o exp. tank, with water filling system
434
- - Without coil protection
E - Epoxy coil-protection (Gold-fin)
C
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7