AHI Carrier Catalog | Page 416

-- User safety: this contact is connected in series with the water flow switch and can be used for any customer safety loop. -- Water pump control. -- Alert indication: this volt-free contact indicates the presence of a minor fault. -- Alarm indication: this volt-free contact indicates the presence of a major fault that has led to the shutdown of the refrigerant circuit. Remote interface (accessory) This accessory includes a box that can be mounted inside the building. The power supply is provided via a 220 V/24 V transformer supplied. This interface allows access to the same menus as the unit interface and can be installed up to 300 m from the 61AF unit. Operating limits Operating range 61AF Minimum Maximum Condenser Entering water temperature at start-up °C 8 57 Leaving water temperature during operation °C 30 65 Entering/leaving water temperature difference K 3 ** Evaporator Entering air temperature, standard unit* °C -20 40 Entering air temperature, unit with option 11 °C -15 40 * 1 2 3 Note: Do not exceed the maximum operating temperature. Minimum water flow rate, l/s 70 65 Leaving water temperature, °C 60 55 50 45 40 35 30 0.70 0.65 0.60 0.55 0.50 0.45 0.40 0.35 25 35 20 -25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 1 2 45 55 65 Leaving water temperature, °C 61AF 022 61AF 030 61AF 035 1.30 1.25 1.20 1.15 1.10 1.05 1.00 0.95 0.90 0.85 0.80 25 35 25 45 55 65 Leaving water temperature, °C 61AF 045 61AF 055 Entering air temperature, °C Full load Plate heat exchanger water flow rate 61AF Maximum* with hydronic module Maximum** without hydronic module 022 1.6 1.8 1.7 2.4 3.3 3.1 3.3 3.8 3.2 4.6 5.9 6.4 6.1 8.5 030 035 045 055 075 105 * ** 2.40 Minimum water flow rate, l/s HEATING ** Outside temperature: For transport and storage of the 61AF units the minimum and maximum allowable temperatures are -20°C and +50°C. It is recommended that these temperatures are used for transport by container. Refer to the minmum unit flow rate. Minimum water flow rate, l/s 0.75 1 2 2.20 2.00 1.80 1.60 1.40 1.20 1.00 25 35 45 55 65 Leaving water temperature, °C 61AF 075 61AF 105 Maximum flow rate at an available pressure of 15 kPa. Maximum flow rate at a water temperature difference of 3 K in the plate heat ­exchanger. Note: For a domestic hot water application (leaving water temperature = 65°C), the water temperature difference must be at least 8 K for operation at 100% capacity. 416 C A R R I E R 2 0 1 6 / 2 0 1 7