-- User safety: this contact is connected in series
with the water flow switch and can be used for any
customer safety loop.
-- Water pump control.
-- Alert indication: this volt-free contact indicates the
presence of a minor fault.
-- Alarm indication: this volt-free contact indicates the
presence of a major fault that has led to the shutdown of the refrigerant circuit.
Remote interface (accessory)
This accessory includes a box that can be mounted inside
the building. The power supply is provided via a 220 V/24 V
transformer supplied. This interface allows access to the
same menus as the unit interface and can be installed up to
300 m from the 61AF unit.
Operating limits
Operating range
61AF
Minimum Maximum
Condenser
Entering water temperature at start-up
°C
8
57
Leaving water temperature during operation °C
30
65
Entering/leaving water temperature difference K
3
**
Evaporator
Entering air temperature, standard unit*
°C
-20
40
Entering air temperature, unit with option 11 °C
-15
40
*
1
2
3
Note: Do not exceed the maximum operating temperature.
Minimum water flow rate, l/s
70
65
Leaving water temperature, °C
60
55
50
45
40
35
30
0.70
0.65
0.60
0.55
0.50
0.45
0.40
0.35
25
35
20
-25 -20 -15 -10
-5
0
5
10
15 20
25
30
35 40
45
1
2
45
55
65
Leaving water temperature, °C
61AF 022
61AF 030
61AF 035
1.30
1.25
1.20
1.15
1.10
1.05
1.00
0.95
0.90
0.85
0.80
25
35
25
45
55
65
Leaving water temperature, °C
61AF 045
61AF 055
Entering air temperature, °C
Full load
Plate heat exchanger water flow rate
61AF
Maximum*
with hydronic module
Maximum**
without hydronic module
022
1.6
1.8
1.7
2.4
3.3
3.1
3.3
3.8
3.2
4.6
5.9
6.4
6.1
8.5
030
035
045
055
075
105
*
**
2.40
Minimum water flow rate, l/s
HEATING
**
Outside temperature: For transport and storage of the 61AF units the minimum and
maximum allowable temperatures are -20°C and +50°C. It is recommended that these
temperatures are used for transport by container.
Refer to the minmum unit flow rate.
Minimum water flow rate, l/s
0.75
1
2
2.20
2.00
1.80
1.60
1.40
1.20
1.00
25
35
45
55
65
Leaving water temperature, °C
61AF 075
61AF 105
Maximum flow rate at an available pressure of 15 kPa.
Maximum flow rate at a water temperature difference of 3 K in the plate heat
exchanger.
Note: For a domestic hot water application (leaving water temperature = 65°C), the water
temperature difference must be at least 8 K for operation at 100% capacity.