AHI Carrier Catalog | Page 407
HIGH-TEMPERATURE AIR-TO-WATER HEAT PUMPS
61AF 022-105
Physical data
61AF
022
030
035
045
055
075
105
Heating
Full load
performances*
H1
Nominal capacity
kW
20.9
26.3
32.6
44.3
52.2
64.9
101.9
H1
COP
kW/kW
4.15
4.19
4.14
4.4
4.39
3.98
4.25
H1
Eurovent Energy Class
A
A
A
A
A
B
A
H2
Nominal capacity
kW
20.8
25.8
32.4
43.9
52.4
66.8
102.0
H2
COP
kW/kW
3.5
3.51
3.45
3.67
3.7
3.43
3.59
H2
Eurovent Energy Class
A
A
A
A
A
A
A
H3
Nominal capacity
kW
20.9
25.3
32.0
43.5
52.8
68.0
102.0
H3
COP
kW/kW
3.05
3.05
3.0
3.21
3.22
3.01
3.13
H4
Nominal capacity
kW
21.2
24.8
31.7
43.4
54.0
68.1
103.4
H4
COP
kW/kW
2.56
2.56
2.52
2.69
2.71
2.54
2.64
H3
Energy Class
A+
A+
A+
A+
A+
A+
-
H3
SCOP
kW/kW
2.68
2.7
2.77
2.98
3.01
2.8
2.96
Ƞs heat
%
104.0
105 .0
108.0
116.0
117.0
109.0
115.0
Prated
KW
19.0
23.0
30.0
41.0
51.0
58.0
87.0
dB(A)
77.0
78.0
83.0
82.0
84.0
84.0
85.0
Standard unit without hydronic module
kg
343
396
421
509
533
900
1020
Standard unit with hydronic module option
kg
349
403
436
524
549
926
1044
Seasonal
Efficiency**
Sound Power Level Standard Unit
Operating weight
Compressor
One, hermetic scroll 48.3 r/s
Refrigerant
R-407C
Condenser
Direct-expansion plate heat exchanger
Fan
Axial with rotating shroud, Flying Bird IV
Quantity
Total air flow at high speed
l/s
HEATING
†
Two, hermetic scroll 48.3 r/s
1
1
1
1
1
2
2
3770
3748
3736
4035
4036
7479
8072
Evaporator
Grooved copper tubes and aluminium fins
Refrigerant
R-407C
H1
H2
H3
H4
*
**
†
Length
mm
1110
1114
2273
Depth
mm
1327
2100
2100
Height
mm
1330
1330
1330
AIR TREATMENT
Dimensions
Heating mode conditions: Water heat exchanger water entering/leaving temperature 30°C/35°C, fouling factor 0 m2 K/W. Outside air temperature 7°C db/6°C wb,
Heating mode conditions: Water heat exchanger water entering/leaving temperature 40°C/45°C, fouling factor 0 m2 K/W. Outside air temperature 7°C db/6°C wb,
Heating mode conditions: Water heat exchanger water entering/leaving temperature 47°C/55°C, fouling factor 0 m2 K/W. Outside air temperature 7°C db/6°C wb,
Heating mode conditions: Water heat exchanger water entering/leaving temperature 55°C/65°C, fouling factor 0 m2 K/W. Outside air temperature 7°C db/6°C wb,
In accordance with standard EN14511-3:2013
In accordance with standard EN14825:2013, average climate
Weight shown is a guideline only.
CONTROLS
Eurovent certified data
C
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7
407