80AW 150
80
70
Pressure, kPa
60
50
40
30
20
10
0
High speed
Medium speed
0
0
500
1000
0.14
0.28
1500
2000
2500
3000
0.42
0.56
0.70
0.84
Flow, l/h
Low speed
Flow, l/s
Hydraulic charts
Physical data, two-zone kit
HEATING
Dimensions
Unit H x L x D
mm
485 x 450 x 330
Packaging H x L x D
mm
565 x 530 x 410
Unit weight
kg
22
Gross weight
kg
27
Water connections
in
1” male
Operating water pressure
kPa (bar)
100 (1)
Maximum pressure
kPa (bar)
300 (3)
Hydronic data
Hydronic components
Pump
Two water-cooled pumps, three speeds, 70 kPa static pressure
Three-way valve
One modulating valve, 6.3 Kv, switching time (90°) 240 seconds, 230-V, 3-point SPDT actuator
Collector volume
l
1
Draining valve
√
Outside air operating range,
heating and cooling
See Comfort module
Electrical data, two-zone kit
Power supply
V-ph-Hz
230-1-50
Voltage range
V
207-253
Power input
W
260
Sound levels, two-zone kit
Sound power level
Sound pressure level*
dB(A)
dB(A)
Without c
omfort module
With c
omfort module
44
30
46
32
* Measured at 2 m distance, in accordance with UNI EN ISO 3741.
370
C
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7