AIR-TO-WATER HEAT PUMP HEATING SYSTEM 38AW/80AW
Electrical data
38AW
Outdoor unit
38AW
38AW
38AW
38AW
38AW
050
065
090
115
120
150
Power supply
V-ph-Hz
230-1-50
230-1-50
230-1-50
230-1-50
400-3N-50
400-3N-50
Voltage range
V-ph-Hz
198-264
198-264
198-264
198-264
376-424
376-424
Full load current
A
12
12
23
23
15.4
15.4
Fuse rating*
A
16
16
25
25
16
16
Operating current
A
5.3
6.91
9.43
12.22
6.45
8.72
Power consumption
W
1220
1590
2170
2810
2580
3490
Main power wire size
mm
2.5
2.5
4
4
2.5
2.5
Power factor
%
0.95
0.95
0.95
0.95
0.95
0.95
*
²
Time delay fuse
Indoor unit (Comfort module)
80AW 065
M0
Outdoor units
M3
M6
T6
38AW 050H7/ 38AW 065H7
Power supply
V-ph-Hz
230-1-50
230-1-50
230-1-50
400-3N-50
Voltage range
V-ph-Hz
207-253
207-253
207-253
360-440
Power input
kW
-
3
6
6
L1
A
-
13.0
26
8.7
L2
A
-
-
-
8.7
L3
A
-
-
-
8.7
N
A
-
13.0
26
-
Power factor
%
1
1
1
1
Indoor unit power supply and
communication cable - H07 RN-F
mm2
2G x 1
2G x 1
2G x 1
2G x 1
Backup heater power supply
cable - H07 RN-F
mm2
-
3G x 4
3G x 6
5G x 2.5
User interface cable (additional
or remote) - FROH2R
mm2
4 x 0.75
4 x 0.75
4 x 0.75
4 x 0.75
Booster heater power supply
cable - H05VV-F
mm2
3G x 2.5
3G x 2.5
3G x 2.5
3G x 2.5
DHW booster heater activation
cable - FROH2R
mm2
2x1
2x1
2x1
2x1
DHW hot water sensor
cable - FROH2R
mm2
2 x 0.5
2 x 0.5
2 x 0.5
2 x 0.5
Remote outdoor sensor
cable - FROH2R
mm2
2 x 0.5
2 x 0.5
2 x 0.5
2 x 0.5
CONTROLS
AIR TREATMENT
HEATING
Operating current
C
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7
363