AIR-TO-WATER HEAT PUMP HEATING SYSTEM 38AW/80AW
Physical data
38AW/80AW
Outdoor unit (heat pump)
38AW
38AW
38AW
38AW
38AW
38AW
050H7
065H7
090H7
115H7
120H9
150H9
80AWH
80AWH
80AWH
80AWH
80AWH
80AWH
065
065
115
115
150
150
dB(A)
64
65
69
70
68
68
48
Indoor unit (comfort module)
38AW
Sound levels
Sound power level(1) (H3)
Sound pressure level at 4m (H3)
dB(A)
44
45
49
50
48
Sound power level(1) (C1)
dB(A)
64
65
68
70
68
68
Sound pressure level at 4 m(2) (C1)
dB(A)
44
45
48
50
48
48
Dimension, H x L x D
mm
690 x 900
x 320
820 x 900
x 320
1360 x
900 x
320
1360 x
900 x
320
1360 x
900 x
320
1360 x
900 x
320
Operating weight(3)
kg
49
51
88
88
100
100
(2)
Refrigerant
kg
1.17
1.3 6
2.1
2.1
3.9
3.9
CO2
eq.
2.4
2.8
4.4
4.4
8.1
8.1
2
2
2
Compressors
DC Inverter Twin-Rotary
Fans
Variable speed 3 blades fan
Quantity
1
1
2
Air flow
m /h
2620
2820
5970
6360
5770
5770
Maximum connection pipe length
m
50
30
70
70
70
70
3
HEATING
R410A
Circuit charge(3)
Maximum height difference
m
30
30
30
30
30
30
Precharged
length
m
20
20
20
30
30
30
Connections, Liquid / Gas side
inch
1/4 - 1/2
3/8 - 5/8
3/8 - 5/8
3/8 - 5/8
3/8 - 5/8
3/8 - 5/8
Chassis paint colour
Beige
CONTROLS
AIR TREATMENT
*
In accordance with standard EN14511-3:2013
** In accordance with standard EN14825:2013, average climate
C1 Cooling mode conditions: evaporator water entering/leaving temperature 12°C/7°C, outside air temperature 35°C, evaporator fooling factor 0 m² K/W
C2 Cooling mode conditions: evaporator water entering/leaving temperature 23°C/18°C, outside air temperature 35°C, evaporator fooling factor 0 m² K/W
H1 Heating mode conditions: Water heat exchanger water entering/leaving temperature 30°C/35°C, fouling factor 0 m2 K/W. Outside air temperature 7°C db/6°C wb,
H2 Heating mode conditions: Water heat exchanger water entering/leaving temperature 40°C/45°C, fouling factor 0 m2 K/W. Outside air temperature 7°C db/6°C wb,
H3 Heating mode conditions: Water heat exchanger water entering/leaving temperature 47°C/55°C, fouling factor 0 m2 K/W. Outside air temperature 7°C db/6°C wb,
(1) In dB ref=10-12 W, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)).
Measured in accordance with ISO 9614-1.
(2) In dB ref 20µPa, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)).
For information, calculated from the sound power level Lw(A).
(3) Weights are guideline only. Refer to the unit nameplate.
C
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7
361