Physical data
38AW/80AW
Outdoor unit (heat pump)
Indoor unit (comfort module)
38AW
38AW
38AW
38AW
38AW
38AW
050H7
065H7
090H7
115H7
120H9
150H9
80AWH
80AWH
80AWH
80AWH
80AWH
80AWH
065
065
115
115
150
150
40.9
40.9
40.9
40.9
40.9
40.9
80AW
Sound levels
Sound power level(1) (H3)
dB(A)
Sound power level (C1)
dB(A)
40.9
40.9
40.9
40.9
40.9
40.9
Dimension, H x L x D
mm
800 x 450
x 320
800 x 450
x 320
800 x 450
x 320
800 x 450
x 320
800 x 450
x 320
800 x 450
x 320
Operating weight(3)
kg
48
48
50
50
52
52
(1)
Hydronic module
HEATING
Pump
Variable speed circulator
Expansion tank
volume
l
8
8
8
8
8
8
Availabale static pressure (C1)
kPa
70
68
68
65
55
41
Availabale static pressure (H1)
kPa
66
60
54
40
45
25
Availabale static pressure (H2)
kPa
68
64
57
41
50
31
Min. system water content
l
21
28
42
42
42
49
Max. water-side operating pressure
kPa
300
300
300
300
300
300
inch
1M
1M
1M
1M
1M
1M
Water connections with or without hydronic
module
Diameter
Outside tube diameter
mm
25.4 M
25.4 M
25.4 M
25.4 M
25.4 M
25.4 M
Connections, Liquid / Gas side
inch
3/8 - 5/8
3/8 - 5/8
3/8 - 5/8
3/8 - 5/8
3/8 - 5/8
3/8 - 5/8
Chassis paint colour
White
*
In accordance with standard EN14511-3:2013
** In accordance with standard EN14825:2013, average climate
C1 Cooling mode conditions: evaporator water entering/leaving temperature 12°C/7°C, outside air temperature 35°C, evaporator fooling factor 0 m² K/W
C2 Cooling mode conditions: evaporator water entering/leaving temperature 23°C/18°C, outside air temperature 35°C, evaporator fooling factor 0 m² K/W
H1 Heating mode conditions: Water heat exchanger water entering/leaving temperature 30°C/35°C, fouling factor 0 m2 K/W. Outside air temperature 7°C db/6°C wb,
H2 Heating mode conditions: Water heat exchanger water entering/leaving temperature 40°C/45°C, fouling factor 0 m2 K/W. Outside air temperature 7°C db/6°C wb,
H3 Heating mode conditions: Water heat exchanger water entering/leaving temperature 47°C/55°C, fouling factor 0 m2 K/W. Outside air temperature 7°C db/6°C wb,
(1) In dB ref=10-12 W, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)).
Measured in accordance with ISO 9614-1.
(2) In dB ref 20µPa, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)).
For information, calculated from the sound power level Lw(A).
(3) Weights are guideline only. Refer to the unit nameplate.
360
C
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7