AHI Carrier Catalog | Page 343

SINGLE-EFFECT STEAM-FIRED ABSORPTION CHILLERS 16TJ 11-53 Foundation dimensions, mm Figure 3 - 16TJ-11 through 16TJ-42 Figure 5 - 16TJ-51 through 16TJ-53 D D C F F J AA AA K G E G E K BB COOLING BB 150 A A B B 150 C Figure 4 - Details of weld Nut Washer A = 150 mm and more Notes: 1. The machine base has ΓΈ50-mm hole for the anchor bolt. 2. The anchor bolt should be fixed as shown in the detail drawing.Washer should be welded to the base (see Fig. 4) 3. There should be a drain channel around the foundation. 4. The floor surface should be made waterproof to facilitate maintenance work. 5. The surface of the foundation should be made flat. 6. Anchor bolts and nuts are to be supplied by customer. Dimensional data 16TJ Weight, kg Dimensions. mm AA + BB AA BB A B C D E F G J K 11 3800 1900 1900 1890 -- 175 360 800 150 1100 160 900 12 4000 2000 2000 1890 -- 175 360 800 150 1100 160 900 13 4900 2450 2450 2916 -- 175 360 800 150 1100 160 900 14 5100 2550 2550 2916 -- 175 360 800 150 1100 160 900 21 6200 3100 3100 2866 -- 200 400 1000 150 1300 200 1100 22 6500 3250 3250 2866 -- 200 400 1000 150 1300 200 1100 23 7600 3800 3800 3886 -- 200 400 1000 150 1300 200 1100 24 8000 4000 4000 3886 -- 200 400 1000 150 1300 200 1100 31 9800 4900 4900 3836 -- 225 450 1100 150 1400 250 1200 32 10200 5100 5100 3836 -- 225 450 1100 150 1400 250 1200 41 11800 5900 5900 3836 -- 225 450 1150 150 1450 250 1250 42 12300 6150 6150 3836 -- 225 450 1150 150 1450 250 1250 51 16900 8450 8450 3706 130 190 510 1600 180 1960 250 1700 52 18300 9150 9150 4248 130 190 510 1600 180 1960 250 1700 53 19600 9800 9800 4746 130 190 510 1600 180 1960 250 1700 C A R R I E R 2 0 1 6 / 2 0 1 7 343 AIR TREATMENT A HEATING HEATING 80 Base CONTROLS Weld