SINGLE-EFFECT STEAM-FIRED ABSORPTION CHILLERS
16TJ 11-53
Foundation dimensions, mm
Figure 3 - 16TJ-11 through 16TJ-42
Figure 5 - 16TJ-51 through 16TJ-53
D
D
C
F
F
J
AA
AA
K
G
E
G
E
K
BB
COOLING
BB
150
A
A
B
B
150
C
Figure 4 - Details of weld
Nut
Washer
A = 150 mm and more
Notes:
1. The machine base has ΓΈ50-mm hole for the anchor bolt.
2. The anchor bolt should be fixed as shown in the detail drawing.Washer should be
welded to the base (see Fig. 4)
3. There should be a drain channel around the foundation.
4. The floor surface should be made waterproof to facilitate maintenance work.
5. The surface of the foundation should be made flat.
6. Anchor bolts and nuts are to be supplied by customer.
Dimensional data
16TJ
Weight, kg
Dimensions. mm
AA + BB
AA
BB
A
B
C
D
E
F
G
J
K
11
3800
1900
1900
1890
--
175
360
800
150
1100
160
900
12
4000
2000
2000
1890
--
175
360
800
150
1100
160
900
13
4900
2450
2450
2916
--
175
360
800
150
1100
160
900
14
5100
2550
2550
2916
--
175
360
800
150
1100
160
900
21
6200
3100
3100
2866
--
200
400
1000
150
1300
200
1100
22
6500
3250
3250
2866
--
200
400
1000
150
1300
200
1100
23
7600
3800
3800
3886
--
200
400
1000
150
1300
200
1100
24
8000
4000
4000
3886
--
200
400
1000
150
1300
200
1100
31
9800
4900
4900
3836
--
225
450
1100
150
1400
250
1200
32
10200
5100
5100
3836
--
225
450
1100
150
1400
250
1200
41
11800
5900
5900
3836
--
225
450
1150
150
1450
250
1250
42
12300
6150
6150
3836
--
225
450
1150
150
1450
250
1250
51
16900
8450
8450
3706
130
190
510
1600
180
1960
250
1700
52
18300
9150
9150
4248
130
190
510
1600
180
1960
250
1700
53
19600
9800
9800
4746
130
190
510
1600
180
1960
250
1700
C
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7
343
AIR TREATMENT
A
HEATING HEATING
80
Base
CONTROLS
Weld