AHI Carrier Catalog | Page 333

SINGLE-EFFECT STEAM-FIRED ABSORPTION CHILLERS 16TJ 11-53 Component identification 1 2 3 COOLING 4 5 7 6 Legend 9 10 1. Condenser 2. Steam inlet 3. Generator 4. Chilled-water outlet 5. Control panel 6. Evaporator 7. Chilled-water inlet 8. Cooling water inlet 9. Heat exchanger 10. Heat reclaimer 11. Absorber HEATING HEATING 8 11 Scope of supply C A R R I E R 2 0 1 6 / 2 0 1 7 AIR TREATMENT 2. Absorption chiller, comprising: 1. Lower shell -- Evaporator and refrigerant dispersion tray -- Absorber and absorbent dispersion tray with eliminators -- Bases. 2. Upper shell -- Generator with eliminators -- Condenser with eliminators -- Rupture disk. 3. Heat exchangers with refrigerant drain heat reclaimer 4. Pumps -- Absorbent pump with isolating valves -- Refrigerant pump with isolating valves -- Purge pump. 5. Purge unit -- Purge tank with ejector device -- Diaphram valves and piping with liquid trap -- Pressure sensor -- Palladium cell with heater. 6. Control panel -- Controller with data display -- LEDs and operation buttons -- Inverter for absorbent pump (option) -- Circuit breaker -- Transformer -- Relays and terminal blocks -- Purge pump operation switch. 7. Locally mounted parts -- Temperature sensors -- Chilled-water flow switch. 8. Interconnecting piping and wiring -- Refrigerant and absorbent piping -- Internal power and control wiring. 9. Initial charge -- Absorbent (lithium bromide) -- Refrigerant (water) -- Inhibitor (lithium molybdate). CONTROLS 1. Standards met The units comply with the following standards: -- ARI 560-2000 -- 2006/42/EC (machine directive) -- 2006/95/EC (low-voltage directive) -- 2004/108/EC (electromagnetic compatibility directive) -- 97/23/EC (pressure equipment directive). 333