AHI Carrier Catalog | Page 331

SINGLE-EFFECT STEAM-FIRED ABSORPTION CHILLERS 16TJ 11-53 Physical data Single effect steam-fired absorption chillers 16TJ Cooling capacity kW 11 12 13 14 21 22 23 24 352 422 527 633 738 844 985 1125 Flow rate l/s 15.1 18.2 22.7 27.3 31.7 36.4 42.5 48.3 Pressure drops kPa 50 51 64 67 60 64 42 45 Connection (ANSI) in 4 4 4 4 5 5 6 6 Retention volume m3 0.12 0.13 0.15 0.17 0.22 0.25 0.29 0.31 COOLING Chilled water system* Cooling water system* Flow rate l/s 22.7 27.3 34.2 40.8 47.8 54.4 63.6 72.8 Pressure drops kPa 34 37 32 36 32 35 65 70 Connection (ANSI) in 5 5 5 5 6 6 8 8 Retention volume m3 0.33 0.37 0.41 0.45 0.58 0.63 0.69 0.76 Steam system Consumption kg/h 780 940 1170 1410 1640 1880 2190 2500 Steam inlet (ANSI) in 5 5 5 5 6 6 8 8 Drain outlet (ANSI) in 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2 Control valve in 2 2 2-1/2 2-1/2 2-1/2 3 3 4 Shutoff valve in 2 2 2-1/2 2-1/2 2-1/2 3 3 4 mm 2690 2690 3690 3690 3790 3790 4850 4850 mm 2200 2200 2200 2200 2350 2350 2370 2370 Width mm 1400 1400 1400 1400 1560 1560 1560 1560 Tube removal space mm 2400 2400 3400 3400 3400 3400 4500 4500 Weight Operating weight kg 4000 4300 5100 5400 6700 6900 7900 8300 Max shipping weight** kg 3500 3700 4500 4700 5800 6000 6900 7200 Power supply V-ph-Hz 400-3-50 Apparent power kVA 4.0 4.0 4.0 4.0 5.8 5.8 5.9 5.9 Total electric current A 6.1 6.1 6.1 6.1 8.8 8.8 8.9 8.9 Absorbent pump, power input kW 1.1 1.1 1.1 1.1 2.2 2.2 2.2 2.2 Absorbent pump, electric current A 2.8 2.8 2.8 2.8 5.5 5.5 5.5 5.5 Refrigerant pump, power input kW 0.2 0.2 0.2 0.2 0.2 0.2 0.3 0.3 Refrigerant pump, electric current A 1.3 1.3 1.3 1.3 1.3 1.3 1.4 1.4 Purge pump, power input kW 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 Purge pump, electric current A 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 PD cell heater kW 0.038 0.038 0.038 0.038 0.038 0.038 0.038 0.038 Control circuit kW 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 * ** In accordance with ARI 560 - 2000 12.2 / 6.7 °C (fouling factor = 0.0176 m2 K/kW) 29.4 / 38.4°C (fouling factor = 0.044 m2 K/kW) Saturated steam 100 kPa All sizes shipped as one-piece AIR TREATMENT Length Height HEATING HEATING Dimensions CONTROLS Notes: These performance data are provided to support early design activity. For selection outside ARI operating conditions contact Carrier. C A R R I E R 2 0 1 6 / 2 0 1 7 331