AHI Carrier Catalog | Page 283

SINGLE-STAGE CENTRIFUGAL LIQUID CHILLERS 19XR/XRV heat exchanger frame size Compressor frame size 3 4 5 5 6 7 7 8 XR3 XR3 XR3 XR4 XR4 XR4 XR5 XR5 Dimensions (mm) Length Min Max Width Min Max Height Min Max 4230 4365 4390 4390 4415 5050 5160 5200 1670 1880 1995 2055 2145 2430 2470 2710 1800 1880 1995 2301 2480 2935 2935 3165 2055 2140 2150 2250 2365 2850 3015 3040 2465 2550 2720 2915 2970 3283 3283 3335 4820 4950 4980 4980 5005 5210 5210 5845 heat exchanger frame size Compressor frame size Weight (kg) net (chiller + R134a) operating (net + water) R134a Min Max Min Max Min Max 3 4 5 5 6 7 7 8 6780 7180 8090 8950 9500 13045 15500 18035 390 508 674 674 740 1168 1168 1309 XR3 XR3 XR3 XR4 XR4 XR4 XR5 XR5 8100 9180 10890 12680 13430 16835 20420 23800 7200 7985 9145 10000 10785 14950 17400 20725 8700 10200 12160 13950 14995 18700 22760 26870 277 381 493 493 546 836 836 984 COOLING Physical data ■■ Variable speed compressor capability – improvement of part load efficiency and electrical performance. ■■ Heat exchangers certified by the European pressure vessels code (PED), and all mar ine code certifications. ■■ International Chiller Visual Control (ICVC) -a large english LCD (liquid crystal display) features 4 menu-specific soft keys. The default display offers all in one glance review of key chiller operation data, simplifying the interaction between chiller and user. Options/accessories ■■ Two types of unit-mounted variable frequency drives (VFDs): standard and high tier, to match different customer requirements in terms of cost and electrical performances ■■ Refrigerant isolation valves allow the refrigerant to be stored inside the chiller during service ■■ Hot gaz by-pass for surge prevention during operation at high condensing temperature or for optimized operation at low load conditions ■■ Spring isolators adapted for all chiller configurations ■■ Unit-mounted starter reduces machine installation time and expense C A R R I E R 2 0 1 6 / 2 0 1 7 ■■ High-voltage motors available: 3000 V, 3300V, 6300V, 10 kV, 11 kV, 50 Hz or 60 Hz ■■ CCN/JBus or CCN/BACnet: remote connection ■■ 21 bar water heat exchanger ■■ Waterbox with flanges and counterflanges ■■ Delivered in multiple sections to facilitate the installation ■■ Refrigerant leak detector module : unit-mounted sensor (not compatible with 19XRV VFD) 283 AIR TREATMENT ■■ Nominal cooling capacities from 1000 to 5300 kW. ■■ Mix-match capabilities – a complete line of compressors and heat exchangers to ensure the optimal combination of machine components regardless of capacity, lift and efficiency specifications. ■■ Hermetic compressor – elimination of leak risks from the compressor/motor shaft sealing in an open compressor. ■■ Single-stage compressor with special features – aerodynamically contoured impellers, variable inlet guide vanes and movable diffusers for better compressor part and full-load operating efficiency. CONTROLS Features and advantages HEATING HEATING Data for unit with two-pass nozzle-in-head water boxes being at the same end (compressor end / DS code)