Operating limits, standard units * ** Evaporator water flow rates 30HXC Minimum flow rate, l/s* Maximum flow rate, l/s** Open loop Closed loop 080-110 120-130 140-155 175-190 200 230-285 310-375 2.3 3.1 3.7 4.3 4.9 6.7 8 7 9.3 11.1 13 14.8 20.1 24 28.2 37.1 44.5 51.9 59.2 80.4 95.9 Based on a velocity of 0.3 m/s in a closed loop and 0.9 m/s in an open loop. Based on a water velocity of 3.6 m/s. * 30HXC Minimum flow rate, Maximum flow rate, l/s l/s* 080-090 100 110 120-130 140-155 175-190 200 230 260-285 310 345-375 5.2 6.5 7.4 8.3 9.4 11.5 14.1 16.3 18.3 20.9 23 20.8 25.9 29.6 33.4 37.8 45.9 56.3 65.2 73.4 83.7 91.9 The maximum flow rate corresponds to a pressure drop of 100 kPa. Operating range, standard units 58 Condenser entering water temperature, °C COOLING Condenser water flow rates 50 B 45 A 35 Notes: 1. Evaporator and condenser Δ T = 5 K 2. For start-up at full load with a condenser water entering temperature below 20°C, a three-way valve must be used to maintain the correct condensing temperature. 3. Maximum condenser water leaving temperature 50°C (at full load). 4. For low evaporator leaving water temperatures <+4°C and >-10°C please order option 6. A Standard unit operating at full load. B Standard unit operating at reduced load. C Units operating with head pressure control with analogue water control valve. For transient operating modes (start-up and part load) the unit can operate down to a condenser entering water temperature of 13°C. 30 25 20 C 15 13 4 5 10 13 15 °C Additional operating range for high condensing temperature units and non-reversible heat pumps. Evaporator leaving water temperature, °C 244 C A R R I E R 2 0 1 6 / 2 0 1 7