Evaporator Entering water temperature at start-up |
° C |
7.5 * |
27 |
|
Leaving water temperature during |
° C |
5 ** |
20 |
|
operation |
||||
Entering / leaving water temperature |
K |
2.5 |
7 |
|
difference |
||||
Condenser Entering water temperature at start-up |
° C |
15 *** |
55 **** |
|
Leaving water temperature during |
° C |
20 |
60 |
|
operation |
||||
Entering / leaving water temperature difference |
K |
2.5 |
18 |
|
* |
For entering water temperatures below 7.5 ° C at start-up , contact Carrier . |
|||
** |
If the leaving water temperature is below 5 ° C , a frost protection solution must |
|||
be used . Please refer to option 6 for evaporator leaving water low-temperature | ||||
applications (< 5 ° C ). | ||||
*** |
For applications with a condenser entering temperature below 15 ° C the use of a |
|||
three-way valve is recommended . This three-way valve can be controlled by the 0-10 | ||||
V analogue output of the Pro-Dialog + control . | ||||
**** For a water flow rate that corresponds to a maximum water-side temperature | ||||
difference of 5 K . |
Evaporator Entering water temperature at start-up |
° C |
7.5 * |
27 |
|
Leaving water temperature during |
° C |
5 ** |
20 |
|
operation |
||||
Entering / leaving water temperature |
K |
2.5 |
7 |
|
difference |
||||
Condenser without hydronic kit Entering air temperature at start-up + during operation |
° C |
10-15 *** |
40-45 **** |
|
Condenser with option 270V ( kit with variable-speed pump ) | ||||
Entering air temperature at start-up + during operation |
° C |
-10 † |
40-45 **** |
|
* |
For entering water temperatures below 7.5 ° C at start-up , contact Carrier . |
|||
** |
If the leaving water temperature is below 5 ° C , a frost protection solution must be used . |
|||
Please refer to option 6 for evaporator leaving water low-temperature applications (< 5 ° C ). | ||||
*** |
The minimum entering air temperature is based on the drycooler selection . |
|||
**** The maximum entering air temperature is based on the drycooler selection . | ||||
† |
For applications with a low condenser entering air temperature the use of a three-way |
|||
valve is recommended . This thre-way valve can be controlled by the 0-10 V analogue | ||||
output of the Pro-Dialog + control . |
Evaporator Entering water temperature at start-up |
° C |
-9.5* |
27 |
|
Leaving water temperature during |
° C |
-12* |
20 |
|
operation |
||||
Entering / leaving water temperature |
K |
2.5 |
3 |
|
difference |
||||
Condenser Entering water temperature at start-up |
° C |
15 ** |
55 *** |
|
Leaving water temperature during |
° C |
20 |
60 |
|
operation |
||||
Entering / leaving water temperature difference |
K |
2.5 |
18 |
|
Note : Do not exceed the maximum operating temperature . | ||||
* |
A frost protection solution must be used . |
|||
** |
For applications with a condenser entering temperature below 15 ° C the use of a |
|||
three-way valve is recommended . This three-way valve can be controlled by the 0-10 | ||||
V analogue output of the Pro-Dialog + control . | ||||
*** |
For a water flow rate that corresponds to a maximum water-side temperature |
|||
difference of 5 K . |
Evaporator Entering water temperature at start-up |
° C |
7.5 * |
27 |
Leaving water temperature during |
° C |
5 ** |
20 |
operation |
|||
Entering / leaving water temperature |
K |
2,5 |
7 |
difference |
|||
Air entering temperature ( at start-up and during operation )*** Air entering temperature ( fixed-speed fan ) |
° C |
0 *** |
35 to 48 ‡ |
Air entering temperature ( variable-speed
° C
|
-10 to -20 † |
35 to 48 ‡ |
|
fan ) |
Condenser leaving water temperature , ° C |
|
Condensing temperatre , ° C
65 60 55 50 45 40 35 30 25 20
|
Medium temperature application
Standard
-2 0 2 4 6 8 10 12 14 16 18 20
Evaporator leaving water temperature , ° C
|